Multiple Dryer Venting
A main vent can be used for venting a group of dryers. The
main vent should be sized to remove 200 CFM of air per
dryer. Large-capacity lint screens of proper design may be
used in the main vent if checked and cleaned frequently. The
room where the dryers are located should have make-up air
equal to or greater than the CFM of all the dryers in the room.
A back-draft damper kit is needed and is available from a
commercial laundry distributor; it should be installed in the
vent of each dryer to prevent exhausted air from returning into
the dryers and to keep the exhaust in balance within the main
vent. Unobstructed return air openings are required.
Each vent should enter the main vent at an angle pointing in the
direction of the airflow. Vents entering from the opposite side
should be staggered to reduce the exhausted air from interfering
with the other vents.
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning fluid fumes. Fumes create
acids which, when drawn through the dryer heating units, can
damage dryers and items being dried.
A clean-out cover should be located on the main vent for periodic
cleaning of the vent system.
If an exhaust hood cannot be used:
The outside end of the main vent should have a sweep elbow
directed downward. If the main vent travels vertically through the
roof, rather than through the wall, install a 180° sweep elbow on
the end of the vent at least 2 ft. (610 mm) above the highest part
of the building. The opening in the wall or roof shall have a
diameter 1/2" (13 mm) larger than the vent diameter. The vent
should be centered in the opening.
Do not install screening or cap over the end of the vent.
30˚ max.
air flow
A. Individual dryer vent
B. Main vent
A
B
12" min.
(305 mm)
24" min.
(610 mm)
A
A. Exhaust hood or elbow
B. Wall
C. Main collector vent
D. Horizontal vent
E. 180° sweep elbow
F. Vertical vent
G. Roof
E
B
G
C
D
2 ft. (610 mm)
min. above
highest point
of building
F
C
Min. 12" (305 mm) clearance
above any accumulation
of snow, ice, or debris such
as leaves.