Power Connection For Deluxe
Series (2200 & 3200)
The Zoneline 2200 and 3200 series units have discrete
heater wattages. Each unit has a factory installed heater and
must be installed on an electrical circuit with sufficient over-
current protection to carry the amperage load of the unit.
See specifications on page 52 for model number
nomenclature, heater amperage, and minimum circuit
ampacity for the particular Zoneline model. To determine
maximum connected load for individual model see page 54
and 55.
230/208 Volt Unit Installation - Line Cord Connected Units
Zoneline 2200 and 3200 series units for installation on 230
or 208 volt circuits have a factory installed line cord with a
plug conforming to NEC standards for the circuit amperage.
Graphic representation of the wall receptacles are shown on
page 38. The line cord length is also shown on page 38.
230/208 Volt Unit Installation - Permanent Connected Units
If a permanent, or direct wired, installation of a 230 or 208
volt units is desired, a junction box kit, RAK4002, is available
to allow direct connection when the 208/230 volt chassis is
installed with the appropriate electrical sub-base. When the
cord set is enclosed by the RAK4002 and the sub-base chase
way RAK205CW, the wiring is totally enclosed and the unit is
considered to be permanently connected. (correct ampacity
RAK204 series sub-base required)
If an installation using flexible conduit is desired, the
RAK4002 kit mounts to the chassis to form an enclosed
junction box with a removable front panel for access to the
unit wiring. A 7/8" diameter hole in the bottom of the
enclosure enables field supplied rigid or flexible conduit to
be connected to the kit. A wiring harness of three
conductors and an in-line connector is included with the
RAK4002.
The factory installed line cord must be cut off approximately
8" from where it comes through the barrier, or bulkhead, of
the unit. Strip insulation off 3/4" of each conductor to
expose wire for field connection. These wires are then
connected to the building wiring by field supplied
connectors.
265 or 277 Volt Unit Installation - Permanent Connected
Units
National Electric Code (Article 440 Section G) requires
permanent connection for units connected to power sources
over 250 volts, therefore these units must be permanently
connected (direct wired).
Zoneline 2200 or 3200 series units rated for installation on
265 volt circuits have discrete heater wattages and the
appropriate cord set to match the 265 volt sub-base
receptacle installed in this sub-base. When installed with the
correct sub-base and chaseway the wiring is totally enclosed
and the installation is considered to be permanently
connected.
If an installation using flexible conduit is desired, the 7/8"
diameter hole in the bottom of the RAK4002 junction box
enables field supplied rigid or flexible conduit to be
connected to the unit. A knockout is provided in the
junction box for the installation of a field supplied cartridge
type fuse, if required. A wiring harness of three conductors
and an in-line connector is included with the RAK4002.
This wiring harness can be ordered separately as
RAK4002CW.
When direct connecting the unit, connections to the
RAK4002
Installed
building wiring should be made in the junction box with
field supplied connectors.
All wiring must conform to local electrical regulations and
codes.
RAK4002