44
Unit Does Not Start-up
Power Switch Light is Off
Possible Cause
Solution
Switch not on
Turn on switch
No power to outlet
Check circuit breaker and wiring
Unit not plugged in
Plug in the unit
Power Switch Light is On and the Thermostat Light is Off
Possible Cause
Solution
No power to thermostat
Check wiring for loose, broken or frayed
connections
connections
Check transformer for 24v output to thermostat
Power Switch Light is On and the Thermostat Light is On
Possible Cause
Solution
Thermostat is not set up properly
Check thermostat set up in the guide.
Press fan ON switch to check evaporator fan only
Unit is Operating and Blows Evaporator Air, but the Supply
Air is Not Colder Than the Return Air from the Cellar
Air is Not Colder Than the Return Air from the Cellar
Possible Cause
Solution
Thermostat not set up properly
Check thermostat setup in the manufacture’s
thermostat guide
thermostat guide
Compressor not operating
High pressure switch open (button up) (see
below)
Condenser airflow is blocked
Remove blockage
Clean filter and coil (if needed)
Clean filter and coil (if needed)
Head Pressure (HP) switch is open
Reset HP switch
See reset instructions on
page 50