Alarms Wire-Wrap Field
Terminate the alarm leads from the CO alarm system to the HMS-318 List 3 shelf. The Alarms wire-wrap field (TB2, 
see 
) is a 26-pin wire-wrap connector and provides a central connection point to the Normally Closed 
(NC), Common (COM), and Normally Open (NO) relay contacts for installing optional alarm input connections (see 
 for Alarm descriptions). When an alarm is not active, there is continuity between the NC and 
COM connections; when an alarm is active, there is continuity between the NO and COM connections.
Figure 1-4. Alarms Wire-Wrap Field (TB2)
Alarm Cutoff (ACO)
The Alarm Cutoff (ACO) function silences active audible alarms. Alarm cutoff can be achieved by pressing the ACO 
button on the front panel of the Management Unit (for example, HMU-319) or by connecting the ACO pin 22 on the 
HMS-318 List 3 shelf Alarms wire-wrap field (see 
 on this page and 
) to ground through an 
external NO push button switch. The ACO lead can be daisy-chained to other shelves for multi-shelf applications in 
the same equipment rack.
!
IMPORTANT
Before making power connections (CO primary power feeds A and B) to the HMS-318 List 3 shelf, 
ensure that the Main CO power breaker is off. Otherwise, severe injury to the installer or damage 
to the unit may result.
Note:
 The NO and COM alarm relay connections can be daisy-chained between HMS-318 List 3 shelves 
for multi-shelf applications in the same equipment rack.
NC
C NO
CR IT
AUD
CR IT
VIS
MAJ
AUD
MAJ
VIS
MIN
AUD
MIN
VIS
SYS
ID
ACO
1
2
3
4
5
6
7
8
9
10 11
12
13
14
15
16
17 18
19 20
21
22
0
6
-1
2
6
1
R
1
ALARMS
23 24
GND
E XT
TEMP
25
26
NO COM
    FAN