State Industries 650A Manuel D’Utilisation

Page de 37
2
FOrEwOrD
The design of the GPG 540A through 740A models complies with 
ANSI Z21.10.3/CSA 4.3 as an automatic circulating tank and an 
automatic instantaneous type heater. The GPV 540A through 
740A models are designed for sidewall venting and direct venting 
applications and are certified under UL 795. 
Detailed installation diagrams are found in this manual. These 
diagrams  will  serve  to  provide  the  installer  with  a  reference 
for the materials and methods of piping necessary. It is highly 
essential that all water, gas piping and wiring be installed as 
shown on the diagrams.
Particular  attention  should  be  given  to  the  installation  of 
thermometers at the locations indicated on the diagrams, as 
these  are  necessary  for  checking  the  proper  functioning  of 
the heater.
THE  HEATER  IS  DESIGNED  TO  OPERATE  ONLY  ON 
NATURAL GAS. 
THESE  HEATERS  MUST  NOT  BE  INSTALLED  ON 
COMBUSTIBLE FLOORS.
rOUGH-iN DiMENSiONS
STANDArD BArOMETriC DrAFT CONTrOL 
GPG MODELS
 HOriZONTAL & DirECT VENTiNG
GPV MODELS
ALL DiMENSiONS iN iNCHES (MiLLiMETErS)
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Gas 
Approx.
    Models 
Conn. 
Ship. wt.
  GPG/GPV 
80 3/4 
73 
32 1/4 
26 1/2 
93 
29 1/2 
48 1/2 
1* 
950
 
540A 
2,051 
1,854 
819 
229 
152 
673 
2,362 
749 
1,232 
25.4 
431 kg
  GPG/GPV 
80 3/4 
73 
32 1/4 
26 1/2 
93 
29 1/2 
48 1/2 
1* 
950
 
650A 
2,051 
1,854 
819 
229 
203 
673 
2,362 
749 
1,232 
25.4 
431 kg
  GPG/GPV 
80 3/4 
73 
32 1/4 
26 1/2 
93 
29 1/2 
48 1/2 
1* 
950
 
740A 
2,051 
1,854 
819 
229 
203 
673 
2,362 
749 
1,232 
25.4 
431 kg
*Minimum gas supply pipe is 1 1/4”, reference Table 7 for gas supply pipe size.
 
 
Storage 
input rating 
recovery rating 
recovery rating 
Current Draw
 
 
Capacity 
BTU/Hr. 
GPH 
GPH 
120V
 
 Models 
U.S. Gals. (Litres) 
Nat. 
100°F rise 
140°F rise 
60Hz 1 Phase
  GPG/GPV-540A 
85 (261) 
540,000 
523.6 
374 
  GPG/GPV-650A 
85 (261) 
650,000 
630 
450 
  GPG/GPV-740A 
85 (261) 
740,000 
718 
512 
 
 
 
 
 
 
 
Based on 80% thermal efficiency obtained in State engineering laboratories.
NOTE: To compensate for the effects of high altitude areas above 2000 feet, recovery ratings should be reduced approximately 
 
4% for every 1000 feet above sea level.
6.0 Amps
MAXiMUM TOTAL 75 EQUiVALENT 
FEET  iNTAkE  AND  EXHAUST 
ALLOwED.