1.  Check gas line pressure with a manometer.
  Set initial gas line pressure at 9-10” w.c. before turning the 
heater “ON”.
  Read gas line pressure and gas manifold pressure when the 
heater main gas is “ON”.
  Adjust gas line regulator setting if the gas line pressure drops 
below 8” w.c. when heater main gas is “ON”.
  Check heater gas manifold pressure (see Table 10) using a 
manometer  connected  to  the  manifold  pressure  tap  on  the 
Robertshaw gas control valve, see Figure 10.
important Note: Use gas manifold pressure as initial setup 
only. The final air and gas settings should be based on fire 
rate and flue gas 0
2
/C0
2
 reading, see Table 10 for normal 0
2
/
C0
2
 reading.
 
 wArNiNG
Excessive  gas  line  pressure  drop  and/or  burner  manifold 
pressure  too  low  may  cause  burner  start/operate  with 
excessive noise!
2.  Cycle the burner “ON” and “OFF” several times to check 
its  operation.  Make  sure  the  gas  line  pressure  is  below  
14” w.c. when burner is “OFF”. If gas line pressure exceeds 
14”  w.c.  when  the  burner  is  off,  the  gas  supply  line  size 
must be increased to correct this problem (see Table 9 for 
gas pipe size).
3.  Check the operation of the limiting and operating controls.
4.  Check the vent system seams and joints and ensure that there 
is no discharge of flue products into the room. For standard 
vertical vent systems, check the barometric damper control to 
make sure it operates freely and there is no discharge of flue 
products into the room.
5.  Check the input rate by clocking the gas meter.
ADJUSTMENT PrOCEDUrE FOr FirE-rATE, 
LOw NOX AND HiGH ELEVATiON (Fine-Tune)
An acceptable input rate is within 2% of the rated input for the 
model. Should it be necessary to adjust the gas pressure to the 
burner and/or air damper of the blower to obtain the full input rate, 
these steps should be followed:
 
 
wArNiNG
Never  set  burner  combustion  too  lean  (causing  noisy 
operation)  or  too  rich  (causing  combustion  chamber 
premature failure) see Table 10 for proper settings.
 
 wArNiNG
Never set air damper outside of its adjustment range of the 
rated fire rate unless authorized by a state service center.
important Note: Final gas and air settings should be based on flue 
gas CO
2
 or O
2
 reading (see Table 10). Increase burner manifold 
pressure will increase fire rate and flue gas CO
2
 reading. Increase 
air  damper  setting  will  decrease  fire  rate  and  decrease  flue 
gas CO
2
 reading. Adjustable air damper is preset for the rated 
fire-rate prior to delivery, should not be re-adjusted unless it’s 
a high elevation application and/or a direct vent (long air intake 
vent) application.
1.  Fire Rate Adjustment (including direct vent installation).
  a. 
Make  sure  the  gas  supply  line  pressure  reads  
 
8” w.c. (2 kPa) or higher when the heater is running.
  b. 
Remove  the  pressure  regulator  cover  screw  
 
(Figure  10)  and  adjust  the  pressure  by  tuning  the 
 
adjustment  screw  w/a  small  screwdriver  clockwise  to  
 
increase  gas  pressure  into  the  burner  and  fire  rate. 
 
Counterclockwise to decrease gas pressure and input  
 
rate.
  c. 
Clock gas meter, repeat above Step (b) to achieve the 
 
specific input rate.
  d. 
Measure  flue  gas  O
2
  and/or  CO
2
  (see  Table  10)  for 
 
acceptable O
2
/CO
2
 range.
   
If the O
2
 or CO
2
 reading is within the acceptable range,  
 
then proceed to Step (f). 
   
If  the  O
2
  or  CO
2
  reading  is  out  of  range,  adjust  air 
 
damper is required.
  e. 
Repeat Steps (b), (c), (d) if air damper is adjusted.
  f. 
Cycle heater ON/OFF.
  g. 
Replace  the  gas  regulator  cover,  pressure  tap  and 
 
tighten the damper center bolt.
2.  Adjustment for Low NOx Emission Application.
  The water heater is preset at factory for Low Nox emission 
combustion.  Due  to  the  installation  variations,  fine-tune 
adjustments may be required. To lower NOx emission level 
(30PPM corrected at 3% O
2
 or lower is required by SCAQMD), 
air  damper  setting  may  need  to  be  slightly  increased.  To 
increase  air  damper  setting,  loosen  the  center  nut  of  the 
inlet  air  damper,  rotate  the  damper  clockwise  slightly,  then 
tighten the center nut. After re-set the air damper, cycle heater  
ON/OFF and check fire-rate and flue gas CO
2
/O
2
 reading.
3.  Adjustment for High Elevation Application
  Installation above 2000 feet sea level require new air damper 
settings. All  the  final  settings  should  be  based  on  flue  gas 
CO
2
/O
2
 reading, see Table 10. To increase air damper setting, 
loosen the center bolt of the inlet air damper, rotate the damper 
clockwise slightly, then tighten the center bolt. After re-setting 
the air damper, cycle heater ON/OFF and check fire-rate and 
flue gas CO
2
/O
2
 reading.
  wArNiNG
UNDEr  NO  CirCUMSTANCES  SHOULD  THE  iNPUT  rATE 
EXCEED THE iNPUT rATE SHOwN iN THE HEATEr rATiNG 
PLATE.    OVErFiriNG  COULD  rESULT  iN  DAMAGE  Or 
SOOTiNG OF THE HEATEr.
SHOULD OVERHEATING OCCUR OR THE GAS SUPPLY FAIL 
TO SHUT OFF, TURN OFF THE MANUAL GAS CONTROL VALVE 
TO THE APPLIANCE.