5.  As soon as the pilot gas valve is energized, check for the 
burner pilot flame through the burner peek-hole. If the pilot 
flame  is  established  inside  the  burner,  then  proceed  to  
Step 6.
•  Turn the burner switch to “OFF” position for at least one minute 
to reset the heater.
•  Check for 24V between “PV” terminal and “MV/PV” terminal 
after  45  seconds  prepurge  cycle  (this  24V  may  only  last  
15 seconds starting after 45S prepurge). If there’s no 24V at 
the “PV” terminal ever, and there’s 24V at “24V” terminal, the 
Honeywell flame control module needs to be replaced.
•  If 24V is detected for a period of 15 seconds, check for the 
changes of gas supply line pressure when the pilot gas valve 
is  energized.  If  no  visible  pressure  change  during  the  pilot 
ignition period, check for loose connection of the pilot valve or 
a defective pilot gas valve.
•  Adjust the pilot gas regulator setting during the pilot ignition 
period  (15  seconds).  Do  not  set  too  much  or  too  little  pilot 
gas. This adjustment should only be performed during the 15 
seconds ignition period. A clockwise or counter-clockwise 0.5 
to 1 turn should be able to correct the problem. Refer to burner 
manual for detailed pilot gas setting procedure.
•  If still no pilot flame inside the burner, check for the spark 
ignitor  wiring,  ignitor  tip  location  and  visually  check  the 
spark (burner pilot assembly needs to be taken out for the 
visual check). Refer to the burner manual for detailed spark 
ignition troubleshooting procedures.
6.  Pilot flame established but not detected by the flame control 
module. Use Micro Amp meter to measure flame signal during 
the  pilot  ignition  period.  Refer  to  burner  manual  for  testing 
procedures.
•  If  pilot  flame  is  confirmed  visually  through  the  burner  
peek hole, and the flame signal is zero, the thermal-cutoff 
safety switch (mounted nearby the flame rod, inside the 
burner mixing chamber) may be broken or check for loose 
wire connections or low gas switch (mounted inside control 
panel) may be broken. If the thermal cutoff switch or low 
gas switch is broken (by checking the switch continuity), 
the  switches  must  be  replaced  before  the  heater  can 
operate again.
•  If it’s confirmed that the thermal cutoff switch is damaged 
(open),  call  the  State  Technical  Center  to  analyze  the 
root cause (too lean combustion) and proper gas/air ratio 
adjustment. Flashback will cause the thermal cutoff switch 
broken (open).
•  If the flame signal is not zero but below 1µA, relocate flame rod 
or replace flame rod will be required. Refer to burner manual 
for detailed procedure of replacing flame rod.
MOTOr rUNS CONTiNUOUSLy, BUrNEr LiGHTS ON
MOMENTAriLy THEN LOCkS OUT Or EXCESSiVE 
ON/OFF CyCLE
Under this condition, the burner will start the purge cycle again, 
then pilot ignition and main flame cycle. If main flame cannot be 
sustained:
1.  Make sure main manual gas valve (right after the Robertshaw 
gas valve) is fully open;
2.  Check for 24V at the Robertshaw gas valve when the main 
gas light is on. If there’s no 24V at the valve, check loose wire 
connection.
3.  Check for gas supply line pressure. The gas line pressure 
before  the  valve  should  be  maintained  at  minimum  
8” w.c. when main flame is “ON”. If the gas line pressure 
drops below 8” w.c. (2 kPa), the service regulator pressure 
setting must be increased to keep 8” w.c. (2 kPa) minimum 
gas  pressure. After  adjusting  the  gas  regulator  setting, 
turn off the heater, make sure the gas line pressure does 
not exceed 14”  w.c. (3.5 kPa) if it does exceed 14” w.c. 
(3.5 kPa) static pressure, the gas supply line size must be 
increased accordingly to avoid gas line pressure exceeding 
14” w.c. (3.5 kPa)
4.  Check the gas valve manifold pressure (refer to Table 10), 
see ADJUSTMENT PROCEDURE to adjust the manifold 
pressure.
5.  Check for defective gas valve for failing to open or shut 
off.
6.  Verify that the air supply is adequate. The air inlet screen 
or blower wheel may be restricted.
7.  Check  the  installation  for  proper  ventilation,  see  AIR 
REQUIREMENTS.
8.  Verify the air switch setting is not too high.
9.  Check the venting system for the correct sizing, excessive 
or insufficient draft, and proper operation of the barometric 
draft control, see VENTING. 
NOiSy BUrNEr OPErATiON
1.  Check  for  flue  gas  excess  O2  or  CO2  reading  (refer  to 
Table 10). If combustion is too lean (flue gas O2 reads more 
than 7.5%), the combustion flame front may not be stable, 
which will cause noisy operation. See ADJUSTMENT.
2.  Check the venting system for the correct sizing, excess or 
insufficient draft, and proper operation of the barometric 
draft control, see VENTING.
3.  If the burner operation is still noisy, then remove the burner, 
examine the burner diffuser, blast-tube tip, anti-flashback 
corrugated tube, center mixing, refer to the burner manual 
for details.
GAS FAiLS TO SHUT OFF
Check for defective gas valve or thermostat. If operation is 
incorrect, replace.
rEPLACEMENT PArTS
Replacement  parts  may  be  ordered  through  State  
dealers,  unauthorized  servicers  or  distributors.    Refer  to  
the Yellow Pages for where to call or contact the State Water 
Heaters, 500 Lindahl Parkway, Ashland City, TN 37015, 1-800-
821-2017 or visit our website at www.statewaterheaters.com  
When ordering parts be sure to state the quantity, part number 
and  description  of  the  items  including  the  complete  model 
and serial number as it appears on the product.  Refer to the 
parts list for more information.