Milliamp output problems
Milliamp output problems and recommended actions
Table 12-6:   
Problem
Possible causes
Recommended actions
No mA output
Wiring problem
Circuit failure
Channel not configured for desired output
Check the power supply and power supply
wiring. See 
Check the mA output wiring.
Check the Fault Action settings. See 
Measure DC voltage across output termi-
nals to verify that the output is active.
Contact Micro Motion.
Loop test failed
Power supply problem
Wiring problem
Circuit failure
Channel not configured for desired output
Incorrect internal/external power configu-
ration
Check the power supply and power supply
wiring. See 
Check the mA output wiring.
Check the Fault Action settings. See 
Contact Micro Motion.
mA output below 4
mA
Open in wiring
Bad output circuit
Process condition below LRV
LRV and URV are not set correctly
Fault condition if fault action is set to inter-
nal zero or downscale
Bad mA receiving device
Check your process conditions against the
values reported by the flowmeter.
Verify that the receiving device, and the
wiring between the transmitter and the re-
ceiving device.
Check the settings of Upper Range Value and
Lower Range Value
.
Check the Fault Action settings. See 
Constant mA output
Incorrect process variable assigned to the
output
Fault condition exists
Non-zero HART address (mA output 1)
Output is configured for loop test mode
Zero calibration failure
Verify the output variable assignments.
View and resolve any existing alarm condi-
tions.
Check the HART address and Loop Current
Mode
.
Check to see if a loop test is in process (the
output is fixed).
Check HART burst mode configuration.
See 
If related to a zero calibration failure, cycle
power to the meter and retry the zeroing
procedure.