S1 Series Emergency Lighting
  S1
Page 1 of 1 
6 Volt 12 to 19.5 Watts Self-Contained Square
Lightolier is a Philips group brand
The S1 Series is a versatile, self-contained emergency lighting fixture. The S1 can be surface mounted, semi-recessed or fully recessed.
Surface Mount
9.0”
(22.9 cm)
3.8”
(9.7 cm)
1.6”
(4.1 cm)
8.0”
(20.3 cm)
2.1”
(5.3 cm)
9.0”
(22.9 cm)
3.8”
(9.7 cm)
11.6”
(29.5 cm)
12.3”
(31.2 cm)
11.6”
(29.5 cm)
Fully Recessed Mount
Unit Battery Capacity
 
 
DC 
 
Watts to 87
1
2
  Voltage 
Unit 
of Rated Voltage*
 
 
 
 
 
1
1
2
 hrs.  2 hrs.  4 hrs.  8 hrs.
 
S112L   
12.0 
9.0 
 
 
S112N   
12.0 
9.0 
— 
— 
 
 
S126N   
26.0 
19.5 
12.5 
* Per NEC Specifications
Features
1.    Illumination:  Illumination is provided by halogen lamps. Plus, the S1 Series 
features a highly reflective polished lens for increased illumination. 12w 
units are furnished with 12 watt halogen lamp. 26w unit is furnished with 7 
watt halogen lamp.
2.    Housing:  Constructed of impact resistant, UL 94 V-0, 5 VA thermoplastic 
frame and backbox. The semi-recessed backbox is constructed of 22 gauge 
steel. The frame is matte white with a black backbox. An acrylic lens is 
standard. A shatter-resistant polycarbonate lens is available.
3.    Electronics:  120/277 VAC dual voltage input with surge-protected, solid-
state circuitry. Charging system is complete with low voltage disconnect, 
AC lockout, brownout protection, AC indicator lamp and test switch.
4.    Battery:  Maintenance free, sealed lead calcium battery has an estimated 
service life of 5 years, and an operating temperature range of 65°F (19°C) to 
85°F (30°C). Maintenance free, sealed nickel cadmium battery has an esti-
mated service life of 10 years, and an operating temperature range of 20°F 
(-7°C) to 95°F (35°C).
  
5.   Input Power Requirements:  120 VAC - 0.096 amps, 10 watts; 277 VAC - 
0.04 amps, 10 watts
Code Compliance
UL 924 listed.
Options
= Voltmeter
= Polycarbonate Lens
Accessories
RMP1 = Semi-Recessed Mounting Kit
    
 
 
SERIES 
BATTERY/ 
MOUNTING 
 
 
WATTAGE 
CONFIGURATION 
S = Surface
R = Fully Recessed
2
NOTES
1) Nickel cadmium units are recommended 
for recessed applications.
2) For semi-recessed applications, order 
the surface mount unit with the RMP1 
accessory. Fully recessed units can only be 
used on suspended ceilings.
3) DC wattage is determined by master unit.
4) 12V remote units can only be remoted 
with 12V single point units.
MASTER UNITS
Lead Calcium 
12L = 6V, 12W
Nickel Cadmium
1
12N = 6V, 12W
26N = 6V, 26W
MASTER UNITS
S1 = Self-Contained 
Emergency Lighting
REMOTE UNITS
3
S1R6 = 6V
S1R12 = 12V
4
Complete Fixture consists of unit and lamps. Select options and accessories below.
How to Specify:
NOTE: IES Photometrics are 