EXCEL 50/100/500/600/800 
EN2B-0092GE51 R1111 
13 
 
ATTRIBUTES 
Each datapoint type has associated with it various parameters which allow the user 
to set, e.g., the user address, the level of access protection, alarm behavior, and 
other options. These parameters are called attributes. Each attribute performs a 
specific function related to the datapoint. A complete list of datapoint types and their 
attributes appears in Table 17 through Table 19. Not all attributes are available for 
every datapoint type. 
 
 
Point refreshing (V1.5.x) 
Four attributes ("Value", "Manual Value", "Operating Mode", and "Alarm Status") will 
be simultaneously refreshed to an XL-Online operator interface. 
 
NOTE: 
A complete list of attributes associated with the various datapoint types 
can be found in the section "List of Datapoint Attributes" on page 38. 
 
 
Access Level 
 
Four levels of protection 
The attribute "Access Level" protects datapoints against unauthorized changes on 
the basis of the password level needed to modify a datapoint. "Access Level" 
attributes between "1" and "4" are assigned to a point. These attributes correspond 
to the four password levels found in the XI581 (not with XCL5010, Excel 100C), 
XI582, and XL-Online operator interfaces and the Excel 50 MMI: 
 
•  Operator level 1: 
Read only. 
•  Operator level 2: 
Read and make limited changes. 
•  Operator level 3: 
Read and make changes. 
•  Operator level 4: 
Programming. 
 
For example, setting the "Access Level" attribute for the datapoint with the user 
address "room temp floor 1" to "2" means that all attributes for this datapoint can 
now only be edited or modified at password level 2 or higher. 
 
 
Acknowledge Alarm (V2.04.xx or higher) 
The attribute "Acknowledge Alarm" allows a controller to acknowledge an alarm for 
a flexible datapoint of the type "feedback" without changing the operating mode. 
The controller takes the point out of alarm as soon as a rising edge is detected on 
the input of the WIA statement writing to the attribute "Acknowledge Alarm". 
 
 
 
Fig. 5. The "Acknowledge Alarm" attribute for WIA statement 
This attribute is a virtual attribute and can be accessed only by a WIA statement in 
CARE. It is not part of the datapoint description and therefore cannot be displayed 
on an MMI or building supervisor.