Honeywell R0512 Manuel D’Utilisation

Page de 86
EXCEL 50/100/500/600/800 
ATTRIBUTES 
 
 
EN2B-0092GE51 R0512 
29 
 
 
 
Motor Run Time 
 
Time to open / time to close 
For actuators controlled via a three-position output, two values (time to open / time 
to close) can be entered in the attribute “Motor Run Time”. This attribute defines the 
time required by the actuator to change from the “Open” to the “Closed” state, and 
vice versa. 
If no value is entered for the “Time to Closed” motor run time, then the “Time to 
Open” motor run time is assumed automatically. In the case of the motor run-on 
time, when reversing directions, 1% of the “Time to Open” motor run time is added 
to the calculated time. 
The three-position output relay energizes when the calculated run time reaches 
500 ms. The stated run time always amounts to 500 ms or a multiple thereof. A 
calculated run time of, for instance, 1215 ms results in an actual run time of 
1000 ms. 
 
 CAUTION 
Regarding motor run time, the behavior of controllers with OS < 2.06.05 
engineered using CARE 4 differs significantly from controllers with OS 
2.06.05 and higher engineered using CARE 7 and higher. See also section 
“Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500 
7.01.02” in Excel CARE – User Guide (EN2B-0182GE51). 
 
 
Off Phase 
 
 
Fig. 16. Off phase 
The attribute "Off Phase" is used in conjunction with flexible datapoints of the type 
"feedback". It defines the duration of the OFF phase on switching down. It is of 
relevance only if the attribute “Switching Down” is set to 0, i.e. if OFF phases are 
selected on switching down. 
 
•  Range: 
0 to 255s 
•  Default value:  10s 
•  Resolution: 
1s 
 
The OFF phase has to be defined for devices with large inertia, such as fans. 
 
 
Operating Mode 
The attribute "Operating Mode" enables the user to switch between manual and 
automatic operation. 
 
 
Automatic 
Under automatic operation, the controller processes the values at the inputs, for 
instance from temperature sensors. For outputs, under automatic operation, the 
status shown by the user/time switch program is adopted, e.g., "Heating circuit 
pump off".