Honeywell R0512 Manuel D’Utilisation

Page de 86
ATTRIBUTES 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
34 
 
whether the off-phase is selected between the single stages, e.g., for ventilators, or 
whether the next lower stage is selected directly, e.g., for electrical air heaters. 
 
Switching down 
Switching down behavior 
3, OFF, 2, OFF, 1, OFF 
3, 2, 1 
 
 
Switch-On Counter 
 
Record switching frequency 
The attribute "Switch-On Counter" gives information about the switching frequency 
of digital datapoints. The change of state from 0 to 1 is counted in each case. 
 
 
Technical Address 
 
Technical address 
An Excel 500/600 controller consists of 16 Distributed input/output modules with a 
total of 128 physical inputs and outputs. The Excel 100C provides 36 physical I/Os 
(see Excel 100C Installation Instructions, form no. EN1R-0144GE51, for technical 
addresses). Where a system requires additional inputs and outputs, several con-
trollers can be connected together. Controllers then communicate with one another 
via the system bus. 
Each physical datapoint within the system must have an address that identifies the 
point uniquely. The technical address contains information about the controller 
number, the I/O module number, and also the input/output number in this module 
(see Fig. 19). 
 
020401
Input/output number
Controller number (set via MMI)
Module number (set via address switc h on eac h I/O module)
 
Fig. 19. Example of a technical address 
Thus, the address 02.04.01 uniquely identifies the first input/output in the fourth 
module of the second controller in your system. 
 
NOTE: 
The Excel 50 controller does not have I/O modules, but its technical 
addresses follow the same pattern, with module numbers referring to 
internal I/O boards. For details, see the Excel 50 Installation Instructions. 
 
  Mapped points (V2.04.xx or higher) 
Datapoints that are mapped only to L
ON
W
ORKS
 network variables are not assigned 
to any I/O board. In this case, the board number (module number) of the technical 
address is zero. 
 
 
Trend Logging 
Up to 20 datapoints (all datapoint types, except for global datapoints) in each 
controller can be trend logged simultaneously. This means changes in the input or 
output value can be stored with the user address, value (or status), date, and time 
for 20 different datapoints. This is achieved by selecting the attribute "Trend 
Logging" to YES in the datapoint description. 
For analog values (see Fig. 20), the value, e.g., 20 
°C / 68 °F, is displayed in 
addition to the user address, date, and time. For digital values (see Fig. 21), the 
status text, e.g., "On", is displayed in addition to the user address, date, and time.