ALARM HANDLING 
EXCEL 50/100/500/600/800 
EN2B-0092GE51 R0512 
50 
 
Alarm 
no. 
alarm text 
English) 
cond. 
code # 
cause/reason 
                                                                                                                               
109 
Hardware Failure 
88 
A Distributed I/O module was removed from the L
ON
W
ORKS
 network or a sensor break or a 
sensor short-circuit or missing NV update from a bound NV was detected on a Distributed 
I/O module. 
110 
Hardware OK 
89 
A missing Distributed I/O module was reconnected to the L
ON
W
ORKS
 network or a missing 
sensor was reconnected on a Distributed I/O module or a sensor break / short-circuit was 
repaired or a missing NV update from a bound NV was supplied. 
111 
M-Bus (XL50, only)  - 
Used only in Excel 50 fixed applications. Shown together with M-Bus-related alarms. 
112 
OVFL crit. alarms 
113 
Critical alarm buffer full. 
113 
OVFL non-crit. al. 
114 
Non-critical alarm buffer full. 
114 
OVFL trend 
115 
Remote trend buffer full. 
115 
NV Bindings lost 
116 
If the network interface has been changed in CARE and the changed application has been 
downloaded, all bindings will be lost. 
116 
pls upload trends! 
117 
The remote trend buffer has reached its notification level and should be uploaded in order 
to avoid trend buffer overflow. 
117 
config data def. 
118 
Configuration data for the remote communication lost or corrupt due to power failure, 
EEPROM fault or uncharged gold cap. 
118 
unauthorized acc. 
119 
Unauthorized telephone number and/or unauthorized password tried to dial in. 
119 
out of memory 
120 
No more memory available for alarm handling. 
120 
Please disconnect!  121 
Front-end X is online while remote trend buffer for front-end Y exceeds the notification 
level. Terminate dial-up connection with the controller in order to allow it to transmit its 
remote trend buffer to front-end Y. 
121 
front-end not avail.  122 
Front-end could not be reached. Line occupied or disconnected. 
122 
config complete 
123 
Configuration for the remote communication received, accepted and complete. 
123 
modem device OK  124 
Response message to the XBS life check. 
124 
C bus error 
125 
No C-Bus communication between remote communication device number and application 
device number. Probably the application device number is missing. 
125 
LON- I/O init start 
126 
Initialization start of the Distributed I/O modules. 
126 
LON- I/O init done 
127 
Initialization of the Distributed I/O modules finished. 
127 
IP-DIO conflict 
128 
Standard I/O module XF5xx plugged with address of already-used DIO module XFL5xx. 
128 
Invalid user ID 
212 
CARE license key tag in the application is incorrect. 
129 
MTO Binding failed  155 
The user has tried to make more “many-to-one-bindings” during controller runtime than 
were specified during CARE engineering. The “many” relation of a “many-to-one-binding” 
(MTO) is specified during CARE engineering. (The entered “many” relation will be used to 
calculate the memory space taken from the controller's application memory for the “many-
to-one-binding”.) 
130 
board missing 
19 
In the event of a module defect or power failure (initialization), this alarm is related to the 
datapoints on this board. The required configuration contains at least one module not 
included in the hardware configuration. 
131 
board present 
108 
In the event of a module defect or power failure (initialization), this alarm is related to the 
datapoints on this board. A module which is part of the required configuration but was 
missing in the hardware configuration has been added to the hardware configuration 
again. 
 
 
 
System Alarms Suppression (V. 2.04.xx or higher) 
System alarms can be suppressed during CARE engineering by inserting the "at" 
sign ("@") at the beginning of the corresponding alarm text in the alarm text file. 
In order to avoid alarm showers at power failure and power return, separate system 
alarms are provided for module power failure and for input failures on the modules 
(see Table 21).