D9412GV2/D7412GV2 | Operation and Installation Guide | 9.0  Off-Board Points 
 
Bosch Security Systems, Inc. | 5/05 | F01U003641B 
35 
 
Table 13: 
Off-Board Point Errors 
 
Error Condition 
Result 
Additional Information 
+/- leg of the data expansion bus has a 
short-circuit to earth ground, with Ground 
Fault Detect enabled 
Ground Fault event 
 
+/- leg of the data expansion bus is 
disconnected 
All POPITs beyond the 
disconnection send Missing 
report 
 
Data expansion bus has a short-circuit 
 
All POPITs send Missing 
report 
 
Pt Bus Trouble event 
When the data expansion bus restores, Pt 
Bus Restore event occurs. If any POPIT is 
connected to the data expansion bus 
without an assigned Point Index, an Extra 
Point event occurs.  
+/- leg of the data expansion bus has a 
short-circuit to the Common terminal on 
the D7212G 
 
All POPITs send Missing 
report 
 
Pt Bus Trouble event 
 
Terminal 28 has a short-circuit to a 
Common terminal 
No Pt Bus Trouble event occurs 
 
Terminal 27 has a short-circuit to a 
Common terminal 
 
Pt Bus Trouble event 
 
Keypad displays: 
SERVC ZONEX 1 
 
Terminals 27 and 28 have a short-circuit 
together 
 
Pt Bus Trouble event 
 
Keypad displays: 
SERVC ZONEX 1 
 
9.1.5 
D9412GV2/D7412GV2 Responses to 
Missing Point Conditions  
The D9412GV2 and D7412GV2 respond to missing 
point conditions based on the point’s programming and 
the armed state of the point’s area. For example, if an 
interior motion detector point is missing during a 
disarmed state, a Missing Trouble event is generated; 
however, if the point is missing while the area is Master 
Armed, a Missing Alarm event is generated. Non-fire, 
24-hour points always generate a Missing Alarm event 
whereas Fire points always generate a Missing Fire 
Trouble event. 
9.2 
D8125, D8127 and D9127 POPIT 
Modules 
D8127 and D9127 POPITs use the D8125 POPEX 
Module to report to the control panel. Each D8125 
supports up to 119 POPIT points. Connect two D8125 
Modules to the D9412GV2 to bring the combined total 
number of POPIT and on-board points to 246. Points 9 
to 127 connect to the first POPEX Module. Points 129 
to 247 connect to the second POPEX Module. The 
D9412GV2 reserves Points 128 and 248 for internal 
use. The control panel annunciates activity only for 
each POPIT, not for each detection device connected 
to the sensor loop.  
There are two versions of the D8127 and D9127 
Modules. Both module enclosures are made of UL 
Listed fire resistant material. D8127T and D9127T 
Modules contain tamper switches. D8127U and 
D9127U Modules include untampered covers. Unless 
the module is mounted in a tampered enclosure, UL 
requires D8127T and D9127T Modules for certificated 
accounts. 
Listings 
The D8125 POPEX and the D8127 and D9127 POPIT 
Modules are UL Listed for Local or Police Connected 
Burglar Alarm, Central Station Burglar Alarm, 
Household Burglar Alarm, Central Station Fire, Local 
Fire, Remote Station Fire, Household Fire, and 
Electrically Actuated Transmitter Applications. 
Refer to the D9412GV2/D7412GV2 Approved 
Applications Compliance Guide
 (P/N: F01U003639) to 
determine the required equipment and enclosures for 
the application.