4.25.3 Load torque high speed frequency control (Pr. 4, Pr. 5, Pr. 270 to Pr. 274)
<Connection diagram>
Load torque high speed frequency control is a function
which automatically sets the operational maximum
frequency according to the load.
The load size during power driving is estimated by
detecting average currents at set timings after a start.
When the load is light, the frequency is increased from
the originally-set frequency. (During regenerative
driving, the frequency is not increased.)
This function is designed to increase speed
automatically under light load, for example to minimize
the incoming/outgoing time in a multi-story parking lot.
Parameter 
Number
Name
Initial 
Value
Setting 
Range
Description
4
Multi-speed setting (high 
speed)
60Hz
0 to 400Hz
Set the higher-speed frequency.
5
Multi-speed setting 
(middle speed)
30Hz
0 to 400Hz
Set the lower-speed frequency.
270
Stop-on contact/load 
torque high-speed 
frequency control 
selection
0
0
Normal operation
1
Stop-on-control (refer to page 214) 
2
Load torque high speed frequency control
3
Stop-on-contact (refer to page 214+ load torque high speed 
frequency control
11
Stop-on-control
E.OLT is invalid 
under stop-on-
control
13
Stop-on-contact + load torque high 
speed frequency control (refer to page 
214)
271 
High-speed setting 
maximum current
50%
0 to 220%
Set the upper and lower limits of the current at high and 
middle speeds.
272 
Middle-speed setting 
minimum current
100%
0 to 220%
273 
Current averaging range
9999
0 to 400Hz
Average current during acceleration from (Pr. 273 
× 1/2) Hz 
to (Pr. 273) Hz can be achieved.
9999
Average current during acceleration from (Pr. 5 
× 1/2) Hz to 
(Pr. 5) Hz is achieved.
274 
Current averaging filter 
time constant
16
1 to 4000
Set the time constant of the primary delay filter relative to 
the output current.
The time constant [ms] is 0.75 
×
 Pr. 274 and the initial value 
is 12ms. 
A larger setting provides higher stability but poorer response.
*1
This parameter allows its setting to be changed during the operation in any operation mode even if "0 (initial value) or 1" is set in Pr.77 Parameter
write selection
.
.......... Specifications differ according to the date assembled. Refer to page 484 to check the SERIAL number.
<Without high-speed 
frequency control>
<With high-speed 
frequency control>
Light
Faster
Whether there is a load or 
not, the lift is moved 
vertically at the same speed.
The lift with a light load or without 
a load is moved faster than the lift 
with a load.
(The output frequency is increased  
only during power driving.)
Mechanical
brake
R/L1
S/L2
T/L3
Motor
MC
STF
CS(X19)
*
Start signal
Load torque high-speed frequency
MCCB
Power supply
U
V
W
Pr. 186 = 19
Sink logic
SD
*
The used terminal changes according to the Pr. 180 to Pr. 189 (input terminal function selection) settings.