Hitachi L200 Manuel D’Utilisation

Page de 280
L200 Inverter
Oper
ations
and Monitor
ing
4–23
Analog Input Current/Voltage Select
The [AT] terminal selects whether the inverter uses the voltage [O] or current [OI] input 
terminals for external frequency control. When intelligent input [AT] is ON, you can set 
the output frequency by applying a current input signal at [OI]-[L]. When the [AT] input 
is OFF, you can apply a voltage input signal at [O]-[L] to set the output frequency. Note 
that you must also set parameter A001 = 01 to enable the analog terminal set for control-
ling the inverter frequency.
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
16
AT
Analog Input 
Voltage/current 
Select
ON
Terminal OI is enabled for current input (uses 
terminal L for power supply return)
OFF
Terminal O is enabled for voltage input (uses 
terminal L for power supply return)
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
A001 = 01
Notes:
If the [AT] option is not assigned to any intelligent 
input terminal, then inverter uses the algebraic sum 
of both the voltage and current inputs for the 
frequency command (and A001=01).
When using either the analog current and voltage 
input terminal, make sure that the [AT] function is 
allocated to an intelligent input terminal.
Be sure to set the frequency source setting 
A001=01 to select the analog input terminals.
Example (default input configuration shown 
for –FU models; –FE models require input 
configuration—see page 
See I/O specs on page 
.
AT
1
2
3
4
5
L
PCS
+ –
4-20 mA, AT=ON
0-10 V, AT=OFF
L
H O OI
AM