Hitachi L200 Manuel D’Utilisation

Page de 280
L200 Inverter
Oper
ations
and Monitor
ing
4–33
Force Terminal Mode
The purpose of this intelligent input is to allow a device to force the inverter to allow 
control of the following two parameters via the control terminals:
• A001 - Frequency source setting (01 = control terminals [FW] and [RV]
• A002 - Run command source setting (01 = control terminals [O] or [OI]
Some applications will require one or both settings above to use a source other than the 
terminals. You may prefer to normally use the inverter’s keypad and potentiometer, or to 
use the ModBus network for control, for example. However, an external device can turn 
ON the [F-TM] input to force the inverter to (temporarily) allow control (frequency 
source and Run command) via control terminals. When the [F-TM] input is OFF, then 
the inverter uses the regular sources specified by A001 and A002 again.
Option 
Code
Terminal 
Symbol
Function Name
Input 
State
Description
51
F-TM
Force Terminal 
Mode
ON
Forces A001=01 (frequency source setting = 
control terminal), and
A002=01(Run command source setting = control 
terminal)
OFF
Inverter applies the user setting for A001 and 
A002 normally
Valid for inputs:
C001, C002, C003, C004, 
C005
Required settings:
A001, A002
Notes:
When changing the [F-TM] state during Run Mode 
(inverter is driving the motor), the inverter will stop 
the motor before the new [F-TM] state takes effect.
Example (requires input configuration—see 
pag
See I/O specs on page 
.
F-TM
1
2
3
4
5
L
PCS