Hitachi L200 Manuel D’Utilisation

Page de 280
Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–38
Frequency Arrival Signals
The Frequency Arrival group of outputs help coordinate external systems with the 
current velocity profile of the inverter. As the name implies, output [FA1] turns ON 
when the output frequency arrives at the standard set frequency (parameter F001). 
Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility. 
For example, you can have an output turn ON at one frequency during acceleration, and 
have it turn OFF at a different frequency during deceleration. All transitions have hyster-
esis to avoid output chatter if the output frequency is near one of the thresholds.
Option 
Code
Terminal 
Symbol
Function Name
Output 
State
Description
01
FA1
Frequency Arrival 
Type 1 – Constant 
Speed
ON
when output to motor is at the set frequency
OFF
when output to motor is OFF, or in any accelera-
tion or deceleration ramp
02
FA2
Frequency Arrival 
Type 2 – Over-
frequency
ON
when output to motor is at or above the set 
frequency thresholds for, even if in acceleration 
or deceleration ramps
OFF
when output to motor is OFF, or during accelera-
tion or deceleration before the respective thresh-
olds are crossed
Valid for outputs:
11, 12, AL0 – AL2
Required settings:
(none)
Notes:
For most applications you will need to use only one 
type of frequency arrival outputs (see examples). 
However, it is possible assign both output terminals 
to output functions [FA1] and [FA2].
For each frequency arrival threshold, the output 
anticipates the threshold (turns ON early) by 1.5Hz.
The output turns OFF as the output frequency 
moves away from the threshold, delayed by 0.5Hz.
The delay time of the output signal is 60 ms 
(nominal).
The example circuit for terminal [12] drives a relay 
coil. Note the use of a diode to prevent the negative-
going turn-off spike generated by the coil from 
damaging the inverter’s output transistor.
Example (default output configuration 
shown—see page 
Inverter output 
terminal circuit
RY
+
FA1
Example for terminals [AL0], [AL1], [AL2] 
(requires output configuration—
see pages 
AL0
AL2
AL1
Inverter logic 
circuit board
See I/O specs 
on page 
FA1
Load
Power
supply
12 11
CM2