Hitachi L200 Manuel D’Utilisation

Page de 280
“A” Group: Standard Functions
Configur
ing
Dr
iv
e P
a
ra
m
e
ters
3–14
Analog Input Settings
The inverter has the capability to accept an external analog input that can command the 
output frequency to the motor. Voltage input (0 –10V) and current input (4–20mA) are 
available on separate terminals ([O] and [OI], respectively). Terminal [L] serves as 
signal ground for the two analog inputs. The analog input settings adjust the curve 
characteristics between the analog input and the frequency output.
Adjusting [O–L] characteristics – In the 
graph to the right, A013 and A014 select the 
active portion of the input voltage range. 
Parameters A011 and A012 select the start 
and end frequency of the converted output 
frequency range, respectively. Together, 
these four parameters define the major line 
segment as shown. When the line does not 
begin at the origin (A011 and A013 > 0), 
then A015 defines whether the inverter 
outputs 0Hz or the A011-specified 
frequency when the analog input value is 
less than the A013 setting. When the input 
voltage is greater than the A014 ending 
value, the inverter outputs the ending 
frequency specified by A012.
Adjusting [OI–L] characteristics – In the 
graph to the right, A103 and A104 select the 
active portion of the input current range. 
Parameters A101 and A102 select the start 
and end frequency of the converted output 
frequency range, respectively. Together, 
these four parameters define the major line 
segment as shown. When the line does not 
begin at the origin (A101 and A103 > 0), 
then A105 defines whether the inverter 
outputs 0Hz or the A101-specified 
frequency when the analog input value is 
less than the A103 setting. When the input 
voltage is greater than the A104 ending 
value, the inverter outputs the ending 
frequency specified by A102.
f
0%
0V
100%
10V
0
%
A012
A011
max frequency
A013
A014
A015=00
A015=01
Input scale
f
0%
04mA
100%
20mA
0
%
A102
A101
max frequency
A103
A104
A105=00
A105=01
Input scale