Mitsubishi Electronics FR-A500 Manuel D’Utilisation

Page de 257
220
SPECIFICATIONS
7.1 Standard Specifications
7.1.1
Model specifications
!
!
!
! 200V class 
Type FR-A520-
""K
0.4
0.75 
1.5 2.2
3.7
5.5 7.5 11
15
18.5
22 30 37 45
55
Applicable
motor capacity
(Note 1)
kW
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
Ou
tp
u
t
Rated capacity
(kVA) (Note 2)
1.1
1.9
3.1
4.2
6.7
9.2
12.6
17.6
23.3
29
34
44
55
67
82
Rated
current (A)
3
5
8
11
17.5
24
33
46
61
76
90
115
145
175
215
Overload current
capacity (Note 3)
150% 60s, 200% 0.5s (inverse-time characteristics)
Voltage (Note 4)
Three-phase, 200 to 220V 50Hz, 200 to 240V 60Hz
Three-phase, 200 to
220V 50Hz,
200 to 230V 60Hz
Regen-
erative
braking
torque
Maximum
value
/Permissi-
ble duty
15% torque/3%ED
(Note 5)
100%
torque/3%ED
(Note 5)
100%
torque/2%ED
(Note 5)
20% torque/continuous
Power
 supply
Rated input AC
voltage, frequency
Three-phase, 200V to 220V 50Hz, 200 to 240V 60Hz
Three-phase, 200 to
220V 50Hz,
200 to 230V 60Hz
Permissible AC
voltage fluctuation
170 to 242V 50Hz, 170 to 264V 60Hz
170 to 242V 50Hz, 170 to
253V 60Hz
Permissible
frequency fluctuation
±5%
Power supply system
capacity (kVA) (Note 6)
1.5
2.5
4.5
5.5
9
12
17
20
28
34
41
52
66
80
100
Protective structure
(JEM 1030)
Enclosed type (IP20) (Note 7)
Open type (IP00)
Cooling system
Self-cooling
Forced air cooling
Approx. weight (kg),with 
DU
2.0
2.5
3.5
3.5
3.5
6.0
6.0
8.0
13.0
13.0
13.0
30.0
40.0
40.0
55.0
Note: 1. The applicable motor capacity indicated is the maximum capacity applicable for use of the
Mitsubishi 4-pole standard motor.
2. The rated output capacity indicated assumes that the output voltage is 220V for 200V class and
440V for 400V class.
3. The % value of the the overload capacity indicates the ratio of the overload current to the
inverter's rated output current. For repeated duty, allow time for the inverter and motor to return to
or below the temperatures under 100% load.
4. The maximum output voltage does not exceed the power supply voltage. You can set the
maximum output voltage to any value below the power supply voltage. However, the  pulse
voltage value of the inverter output side voltage remains unchanged at about 
 that of the power
supply. 
5. Short duration rating 5s
6. The power supply capacity varies with the value of the power supply side inverter impedance
(including those of the input reactor and cables).
7. The open type (IP00) is used when the plug-in option is fitted after removal of the option wiring
port cover.
2