Schneider Electric PM5300 Manuel D’Utilisation
PowerLogic™ PM5300 series user guide
Chapter 3—Hardware Reference
© 2014 Schneider Electric All Rights Reserved
15
Technical Specifications
Electrical Characteristics
Type of measurement: True rms on three-phase
(3P, 3P + N), zero blind
(3P, 3P + N), zero blind
64 samples per cycle
Measurement accuracy
IEC 61557-12
1
PMD/[SD|SS]/K70/0.5
Active Energy
2
Class 0.5S as per IEC 62053-22
Reactive Energy
2
Class 2S as per IEC 62053-23
Active Power
Class 0.5 as per IEC 61557-12
1
Reactive Power
Class 2 as per IEC 61557-12
1
Apparent Power
Class 0.5 as per IEC 61557-12
1
Current, Phase
Class 0.5 as per IEC 61557-12
1
Voltage, L-N
Class 0.5 as per IEC 61557-12
1
Frequency
Class 0.05 as per IEC 61557-12
1
Power Factor
Class 0.5 as per IEC 61557-12
1
Voltage Harmonics
Class 5 as per IEC 61557-12
1
Voltage THD/thd
Class 5 as per IEC 61557-12
1
Current Harmonics
Class 5 as per IEC 61557-12
1
Current THD/thd
Class 5 as per IEC 61557-12
1
MID Directive (2004/22/EC)
Annex B and Annex D (PM5331 and PM5341)
Class C
Class C
Input-voltage (up to 1.0 MV AC max, with voltage transformer)
Nominal Measured Voltage range
UL: 20-347 V L-N/35-600 V L-L
IEC: 20-400 V L-N/35-690 V L-L
(absolute range 35 V L-L to 760 V L-L)
IEC: 20-400 V L-N/35-690 V L-L
(absolute range 35 V L-L to 760 V L-L)
Impedance
5 M Ω
F nom
50/60 Hz
Input-current (configurable for 1 or 5 A secondary CTs)
I nom
5 A
Measured Amps with over range and Crest Factor
Starting current: 5mA
Operating range: 50mA to 8.5A
Operating range: 50mA to 8.5A
Withstand
Continuous 20 A,10s/hr 50 A, 1s/hr 500 A
Impedance
< 0.3 mΩ
F nom
50/60 Hz
Burden
<0.026VA at 8.5A
Frequency measurement
Measurement range
45 to 65 Hz
AC control power
Operating range
100 - 277 V AC L-N / 415 V L-L +/-10%
CAT III 300V class per IEC 61010
CAT III 300V class per IEC 61010
Burden
<5 W,11 VA at 415V L-L
Frequency
45 to 65 Hz
Ride-through time
80 mS typical at 120V AC and maximum burden.
100 mS typical at 230 V AC and maximum burden
100 mS typical at 415 V AC and maximum burden
100 mS typical at 230 V AC and maximum burden
100 mS typical at 415 V AC and maximum burden
DC control power
Operating range
125-250 V DC ±20%
Burden
<4 W at 250 V DC
Ride-through time
50 mS typical at 125 V DC and maximum burden
Outputs
Mechanical
Max output frequency
0.5 Hz maximum (1 second ON /
1 second OFF - minimum times)
1 second OFF - minimum times)
Switching current
250 V AC at 8.0 Amps, 25 k cycles, resistive
30 V DC at 2.0 Amps, 75 k cycles, resistive
30 V DC at 5.0 Amps,12.5 k cycles, resistive
30 V DC at 2.0 Amps, 75 k cycles, resistive
30 V DC at 5.0 Amps,12.5 k cycles, resistive
Isolation
2.5 kV rms
Digital outputs
Max load voltage
40 V DC
Max load current
20 mA
On Resistance
50 Ω max