Drain Pan and Light Shield Removal 
 
To remove the drain pan, remove screws along the front 
face of the drain pan.  Lift the rear of the pan up and out 
of the drain trough.  Slide pan towards you and out.  
Reverse procedure to install. 
 
To remove the light shield, remove screws along the front 
face of the light shield.  Pull the light shield towards you 
and out.  Reverse procedure to reinstall.
 
 
 
 
 
 
 
 
 
SERVICE INSTRUCTIONS  
 
OPERATION CONDITIONS AND PRESSURES 
 
With room ambient temperature of +80 
o
F and cold cabinet (unit cycling on control): 
 
Suction pressure – 5 to 9 psig. 
Head pressure – 210 to 260 psig. 
 
Typical operating pressures for a properly charged unit operating at 0
°F or lower box temperature, check 
pressures immediately before normal off cycle expect a tolerance of ± 5 psig high side, and ±1 psig low side.
 
 
 
 
Light Shield
Drain Pan