Chapter 4: Operation 
29 of 70 
Chapter 4:  Operation 
4-1  Panel Buttons, Indicator Lights, and Switches 
Microprocessor Controllers  
Standard chillers use a microprocessor-based PID controller. These controllers are modular, 
self-contained units that can slide from their mounting housing. They are factory set and 
adjusted; no field adjustment to the internal controls are necessary. Their standard operation 
range is 30ºF to 65ºF (-1ºC to 18ºC). See Figure 7: Typical Portable Chiller Microprocessor 
Controller. 
E5CK Controller 
Indicator 
Name 
Description 
PV 
  8.8.8.8    
Process Value 
LED 
During normal operation, the top LED display on 
the controller displays the actual process 
temperature. It also lists parameter symbols during 
setup and error messages if an error occurs. 
SV 
8.8.8.8
 
Set Value LED 
During normal operation, the green bottom LED 
display on the controller displays the process set 
point you want the chiller to maintain. It also 
displays parameter and pre-set function values 
during set up. 
 
OUT1 
Out 1 LED 
The orange OUT1 LED lights when the control 
output energizes the hot-gas bypass solenoid 
valve. 
 
 
OUT2 
Out 2 LED 
The orange OUT2 LED lights whenever the 
process temperature is four degrees or more above 
the “To Process” setpoint. The compressor then 
comes on and runs until the temperature at the “To 
Process” thermocouple is three degrees below the 
setpoint. 
 
 
MANU 
MANU LED 
The orange MANU LED is not used and does not 
light. 
 
STOP 
Stop LED 
The orange STOP LED is not used. 
 
RMT 
RMT LED  
The orange RMT LED is lit during remote 
communication operation. 
  
 AT 
AT LED 
The orange AT LED flashes during auto-tuning.