Sterling A0554831 Manuel D’Utilisation

Page de 70
2-40 HP Portable Chillers 
Chapter 7: Appendix 
48 of 70 
20 hp, 25 hp, and 30 hp Air-Cooled Portable Chillers 
Nominal operating parameters for air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm per ton 
(9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air. For 50 Hz applications, multiply capacity by 0.83. Nominal 60 
Hz capacity flow rate must be maintained.
 
 
 
Nominal cooling  
Water
Com-  Nom.
 
Power in amps 
e, 460/3/60 f
HP capacity 
c tons 
flow  pressor pump
Discharge air  
1 pump 
2 pumps 
 
no pump  1 pump  2 pump  gpm 
d
hp hp 
openings 
cfm 
rated running rated running
20 
19.4 
18.4 
18.0 
46.5 
2 @ 10
25” x 18.5” 10,200  48.3 42.0 51.4
45.1 
25 
23.9 
22.8 
22.4 
57.2 
2 @ 13
25” x 18.5” 13,300  62.1 48.3 65.2
51.4 
30 
29.2 
28.2 
27.8 
70.2 
2 @ 15
25” x 18.5” 18,150  74.1 64.4 77.2
67.5 
c Based on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air. Optional additional process 
pump hp reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power). 
d  Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump. 
e  An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total 
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 
on page 16), and add it to the chiller rated or running amperage. 
f  Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 0.8 for 575/3/60 amperages. 
g  To convert cfm to cmh, multiply by 1.699. 
 
 
20 hp, 25 hp, and 30 hp air-cooled portable chillers come standard with 4” (101 mm) swivel casters. 
 
 
Com- 
Process connections, in. NPT 
Dimensions 
Weights 
HP 
pressor 1 Pump  2 Pump no pump, 1 pump, no
in inches 
c Dry 
d Ship. d Oper. d e
 hp 
to/from 
to/from 
no 
tank
tank, 
to/from 
height
width depth  lbs.  lbs. 
lbs. 
20 
2 @ 10  2” / 3”  2.5” / 3” 
2.0” 
2” / 3” 
91.4 
34.0 
100.7 2,305 2,605  2,971 
25 
2 @ 13  2” / 3”  2.5” / 3” 
2.0” 
2” / 3” 
91.4 
34.0 
100.7 2,348 2,648  3,014 
30 
2 @ 15  2” / 3”  2.5” / 3” 
2.0” 
2” / 3” 
91.4 
34.0 
100.7 2,610 2,910  3,276 
c  To convert to cm, multiply by 2.54. Add to height dimension based on mounting options. 
d  Weight is for standard chiller. Some optional features will increase weight. Multiply lbs. by 0.454 to calculate Kg
e
 
Operating weight is with a full 80-gallon (303 liter) reservoir tank of water.