Sterling A0554831 Manuel D’Utilisation

Page de 70
2-40 HP Portable Chillers 
Chapter 7: Appendix 
56 of 70 
20 hp through 40 hp Remote Air-Cooled Portable Chillers 
Nominal operating parameters for remote air-cooled models are 50ºF (10ºC) leaving water temperature at 2.4 gpm 
per ton (9.1 lpm per 3.517 kW) with 95ºF (35ºC) ambient air. For 50 Hz applications, multiply capacity by 0.83. 
Nominal 60 Hz capacity flow rate must be maintained.
 
 
Nominal cooling  
Nom. 
Com- 
 
Refrigeration 
Power in amps 
e 
 capacity 
c tons 
water 
pres- 
Nom.
connections 
460/3/60 
f 
 
no 
flow 
sor 
pump
in. dia. ODS 
1 pump 
2 pumps 
HP  pump pump pump gpm 
d
hp 
hp  Discharge Liquid
rated running rated running
20  19.4 18.4 18.0  46.5 
10
13/8” 
7/8” 
43.9 37.6  47.0  40.7 
25  23.8 22.8 22.4  57.2 
13
13/8” 
7/8” 
55.9 42.1  59.0  45.2 
30  29.2 28.2 27.8  70.2 
15
13/8” 
7/8” 
60.0 50.4  63.2  53.5 
40  36.9 35.4 35.0 88.6  40  7.5  15/8” 11/8”
81.9 68.8  85.0  58.0 
c  Based on 50ºF (10ºC) chilled water supply temperature and 95ºF (35ºC) ambient air. Optional additional process 
pump hp reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power). 
d  Based on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump. 
e  An optional oversized process pump adds to the total rated or running chiller amperage. To find the new total 
chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 
on page 16), and add it to the chiller rated or running amperage. 
f  Multiply 460/3/60 amperage by 2.0 for 208-230/3/60 amperages; multiply by 0.8 for 575/3/60 amperages. 
 
Remote air-cooled portable chillers come standard with mounting rails. Remote air-cooled portable 
chillers are charged with 25 psi (172.4 kPa/1.72 bars) nitrogen for shipping purposes. 
 
Com- 
Process connections, in. NPT 
Dimensions 
Weights 
HP 
pressor  1 pump  2 Pump no pump, 1 pump, no
in inches 
c  
Dry 
d Ship. 
d Oper. d e
 
hp 
to/from  to/from  no tank tank, to/from height width depth
lbs. lbs.  lbs. 
20 
2 @ 10  2” / 3” 
2.5” / 3” 
2.0” 
2” / 3” 
43.3” 
34.0” 100.7”
1,299  1,549 
1,965 
25 
2 @ 13  2” / 3” 
2.5” / 3” 
2.0” 
2” / 3” 
43.3” 
34.0” 100.7”
1,305  1,555 
1,971 
30 
2 @ 15  2” / 3” 
2.5” / 3” 
2.0” 
2” / 3” 
43.3” 
34.0” 100.7”
1,607  1,857 
2,273 
40 
40 
2.5” / 3”  2.5” / 3” 
2.5” 
2.5” / 3” 
43.3” 
34.0” 100.7”
2,243  2,470 
2,909 
c  To convert to cm, multiply by 2.54. Add to height dimension based on mounting options. 
d  Weight is for standard chiller. Some optional features will increase weight.  
e  Operating weight is with a full 80-gallon (303 liter) reservoir tank of water.