CONDENSATE DRAIN
The condensate drain hose is routed down from the
evaporator drain pan on the right side of the unit into
the compressor compartment.  There are three
locations that the drain can exit the cabinet.  For a
stand pipe type of drain, the drain hose can exit the
rear of the cabinet.  There is adequate hose length to
reach the floor on the right hand side of the unit.
If the drain is to be hard plumbed, there is a 3/4 inch
pipe connection located on the right hand cabinet
side near the rear and one on the cabinet rear panel.
In these installations the drain tube is to be slipped
over the pipe connection inside of the cabinet.
FIGURE  9B
OPTIONAL REAR DRAIN
See Figures 9A, 9B and 9C.
NOTE: Whichever type of drain connection is used a
“P” trap must be formed.
The side drain requires a water trap for proper drainage.
See Figure 8A.  The drain can be routed through the floor
or through the wall.  
If the drain is to be routed through
an unconditioned space, it must be protected from
freezing
.
  The drain line must be able to be removed from
the unit if it is necessary to remove the unit from the wall.