INSTALLATION INSTRUCTIONS
MOUNTING THE UNIT
When installing a QC unit near an interior wall on the
left side, a minimum of 8 inches is required; 12 inches
is preferred.
When installing a QC unit near an interior wall on the
right side, a minimum of 12 inches is required as
additional space is required to connect the drain.
This clearance is required to allow for the attachment of
the unit to the wall mounting brackets and the side  trim
pieces to the wall.
This unit is to be secured to the wall with the wall
mounting brackets provided.  The unit itself, the supply
duct, and the free blow plenum are suitable for “0”
clearance to combustible material.
NOTE: When a wall sleeve is to be used discard the
brackets shipped with the heat pump and
attache the unit to the sleeve with bracket
supplied with the wall sleeve.
Following are the steps for mounting the QC units for
reference see Figure 13.
 1. Attach wall mounting bracket to the structure wall
with field supplied lag bolts.  The fluid piping
connections are to be within the confines of this
bracket.  See Figure 1 for cabinet openings and
location of fluid coil connection points.
 2. Position the unit in front of the wall mounting
bracket.
 3. Remove the locking screws from the wheels.  Refer
to Figure 11.
 4. Roll the unit up to the wall mounting bracket.  The
unit must be level from side to side.  If any
adjustments are necessary, shim up under the rollers
with sheets of steel or any substance that is not
affected by moisture.
 5. Secure the unit to the wall bracket with provided
#10 hex head sheet metal screws.  There are
prepunched holes in the cabinet sides, and the
bracket has slotted holes to allow for some
misalignment.
 6. Position the bottom trim piece to the unit and attach
with provided screws (dark colored).
 7. Position side trim pieces to the wall and attach with
field supplied screws.  There are two long and two
short pieces supplied.  The long pieces are to
enclose the gap behind the unit.  The short pieces
are to fill the gap behind the cabinet extension or the
free blow plenum box.  They may be cut to suit the
ceiling height or overlap the unit side trim.  There is
sufficient length to trim up to a 10’2” ceiling.
FIGURE  12
REMOVING LOCKING SCREWS FROM WHEELS
MIS-1523
REMOVE SCREWS
FROM WHEELS
BEFORE ROLLING
INTO PLACE