Table 2  - 90 - 50/75/100 SERIES 2 NATURAL GAS
MODEL 90-50
Stock Factory
Btu Value of Natural Gas++
Settings
750
850
950
1000
1050
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
50
Manifold Pressure In W.C.
2.5
4
4
3.5
2.5
2.5
Orifi ce
43331094
43331094
MODEL 90-75
Stock Factory
Btu Value of Natural Gas++
Settings
750
850
950
1000
1050
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
75
Manifold Pressure In W.C.
2.5
3.5
3.5
2.5
2.5
2.5
Orifi ce
43331092
43331092
MODEL 90-100
Stock Factory
Btu Value of Natural Gas++
Settings
750
850
950
1000
1050
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
100
Manifold Pressure In W.C.
2.5
3.5
3.5
2.5
2.5
2.5
Orifi ce
43331090
43331090
++Contact local gas utility or distributor for Btu value of gas.
 BOILERS FOR USE AT HIGH ALTITUDE - UNITED STATES INSTALLATIONS
• Boilers (with exception of 90-75 propane (LP) product) 
are factory equipped for operation at altitudes ranging 
from 0-10,000 feet above sea level. 
• No changes to factory settings are required for installa-
tions from 0-5,000 feet above sea level. 
• For altitudes from 5,000-10,000 feet above sea level 
gas manifold pressure needs to be adjusted based upon 
calorifi c (Btu) value of supply gas (contact local gas 
utility or distributor for this value). 
• For specifi c settings refer to  Table 2  for natural gas 
applications and  Table 3, Page 7  for propane (LP) gas 
applications. 
• Instructions on how to adjust gas manifold pressure 
settings see  Figure 27  and  Figure 28, Page 44 .
Note 90-75 propane (LP) applications for 5,000 - 10,000 
feet above sea level require orifi ce change as well as gas 
manifold pressure adjustment based upon calorifi c (Btu) 
value of supply gas. 
Refer to  Table 2   and  Table 3  for high altitude orifi ce part 
number. For replacing orifi ce refer to specifi c instructions 
included with conversion kit.