Lennox International Inc. GWB9-075IH-2 Manuel D’Utilisation
6
Table 2 - 90 - 50/75/100 SERIES 2 NATURAL GAS
MODEL 90-50
Stock Factory
Btu Value of Natural Gas++
Settings
750
850
950
1000
1050
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
50
–
–
–
–
–
Manifold Pressure In W.C.
2.5
4
4
3.5
2.5
2.5
Orifi ce
43331094
43331094
MODEL 90-75
Stock Factory
Btu Value of Natural Gas++
Settings
750
850
950
1000
1050
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
75
–
–
–
–
–
Manifold Pressure In W.C.
2.5
3.5
3.5
2.5
2.5
2.5
Orifi ce
43331092
43331092
MODEL 90-100
Stock Factory
Btu Value of Natural Gas++
Settings
750
850
950
1000
1050
Altitude in Ft.
0-5,000
5,000-10,000
Normal Input (MBH)
100
–
–
–
–
–
Manifold Pressure In W.C.
2.5
3.5
3.5
2.5
2.5
2.5
Orifi ce
43331090
43331090
++Contact local gas utility or distributor for Btu value of gas.
BOILERS FOR USE AT HIGH ALTITUDE - UNITED STATES INSTALLATIONS
• Boilers (with exception of 90-75 propane (LP) product)
are factory equipped for operation at altitudes ranging
from 0-10,000 feet above sea level.
• No changes to factory settings are required for installa-
tions from 0-5,000 feet above sea level.
• For altitudes from 5,000-10,000 feet above sea level
gas manifold pressure needs to be adjusted based upon
calorifi c (Btu) value of supply gas (contact local gas
utility or distributor for this value).
• For specifi c settings refer to Table 2 for natural gas
applications and Table 3, Page 7 for propane (LP) gas
applications.
• Instructions on how to adjust gas manifold pressure
settings see Figure 27 and Figure 28, Page 44 .
Note 90-75 propane (LP) applications for 5,000 - 10,000
feet above sea level require orifi ce change as well as gas
manifold pressure adjustment based upon calorifi c (Btu)
value of supply gas.
Refer to Table 2 and Table 3 for high altitude orifi ce part
Refer to Table 2 and Table 3 for high altitude orifi ce part
number. For replacing orifi ce refer to specifi c instructions
included with conversion kit.