Specifications 
Connection Type  
Series connected
Agency Listings 
UL 1449, UL 1283, CSA
Protection Modes 
All modes standard (Line to Neutral, 
Line to Ground, Neutral to Ground, 
Line to Line); any combination optional
EMI/RFI Filtering 
Normal mode — 60 dB maximum from 
10 kHz to 500 MHz; Common mode 
50 dB maximum from 10 kHz to 500 MHz
Response Time 
less than .5 nanoseconds
Load Regulation 
1% no load to full load
Enclosure 
NEMA 12 standard; options include 
NEMA 3R, 4, 4X and caseless for 
switchgear applications
Current
Model Number
Surge Current Capability
Dimensions
Rating
Configuration
(xxx=voltage code)
per phase (L-N or L-L+L-G)
(inches)
Weight
A
B
C
D
E
F
Lbs.
30A 
Single Phase L-L
FXXXL30
100kA
24.0
20.0
9.0
21.25
10.0
.44
40
30A
Single Phase L-N
FXXXN30 
100kA
24.0
20.0
9.0
21.25
10.0
.44
35
30A
Split Phase
FXXXS30
100kA
24.0
20.0
9.0
25.25
14.0
.44
45
30A
Three Phase Delta
FXXXD30
100kA
24.0
20.0
9.0
25.25
14.0
.44
50
30A
Three Phase Wye
FXXXY30
100kA
24.0
20.0
9.0
25.25
14.0
.44
60
60A
Single Phase L-L
FXXXL60
100kA
24.0
20.0
9.0
21.25
10.0
.44
40
60A
Single Phase L-N
FXXXN60
100kA
24.0
20.0
9.0
21.25
10.0
.44
35
60A
Split Phase
FXXXS60
100kA
24.0
20.0
9.0
25.25
14.0
.44
45
60A
Three Phase Delta
FXXXD60
100kA
24.0
20.0
9.0
25.25
14.0
.44
50
60A
Three Phase Wye
FXXXY60
100kA
24.0
20.0
9.0
25.25
14.0
.44
60
100A
Single Phase L-L
FXXXL100
150kA
30.0
24.0
9.0
31.25
18.0
.44
65
100A
Single Phase L-N
FXXXN100
150kA
30.0
24.0
9.0
31.25
18.0
.44
60
100A
Split Phase
FXXXS100
150kA
30.0
24.0
9.0
31.25
18.0
.44
70
100A
Three Phase Delta
FXXXD100
150kA
30.0
24.0
9.0
31.25
18.0
.44
70
100A
Three Phase Wye
FXXXY100
150kA
30.0
24.0
9.0
31.25
18.0
.44
80
125A
Single Phase L-L
FXXXL225
150kA
30.0
24.0
9.0
31.25
18.0
.44
65
125A
Single Phase L-N
FXXXN225
150kA
30.0
24.0
9.0
31.25
18.0
.44
60
225A
Split Phase
FXXXS225
150kA
30.0
24.0
9.0
31.25
18.0
.44
70
225A
Three Phase Delta
FXXXD225
150kA
30.0
24.0
9.0
31.25
18.0
.44
70
225A
Three Phase Wye
FXXXY225
150kA
30.0
24.0
9.0
31.25
18.0
.44
80
400A
Three Phase Delta
FXXXD400
150kA
48.0
36.0
12.0
49.25
30.0
.44
275
400A
Three Phase Wye
FXXXY400
150kA
48.0
36.0
12.0
49.25
30.0
.44
300
800A
Three Phase Delta
FXXXD800
choose 200 or 300 kA
60.0
48.0
12.0
-
-
-
500
800A
Three Phase Wye
FXXXY800
choose 200 or 300 kA
60.0
48.0
12.0
-
-
-
530
1200A
Three Phase Delta
FXXXD1200
choose 200 or 300 kA
60.0
48.0
20.0
-
-
-
700
1200A
Three Phase Wye
FXXXY1200
choose 200 or 300 kA
60.0
48.0
20.0
-
-
-
750
2000A
Three Phase Delta
FXXXD2000
choose 200 or 300 kA
60.0
48.0
20.0
-
-
-
875
2000A
Three Phase Wye
FXXXY2000
choose 200 or 300 kA
60.0
48.0
20.0
-
-
-
950
4000A
Three Phase Delta
FXXXD4000
choose 200 or 300 kA
60.0
48.0
20.0
-
-
-
1175
4000A
Three Phase Wye
FXXXY4000
choose 200 or 300 kA
60.0
48.0
20.0
-
-
-
1300
How To Specify The Appropriate Model:
1) Go to Chart A, choose your Current Rating from column one and corresponding Configuration from column two.
2) Follow column two across to column three to determine your Model Number.
3) Refer to Chart B to determine the Voltage Code from the available choices. Substitute the Voltage Code for “XXX.” 
(Use the first three digits of the Voltage Code for split phase and three phase configurations).
4) Finally, to complete your model number, go to the last column or (Monitoring Options) and choose the suffix for Standard Features (-06) or
Optional Features (-03).
Char t A - Active Tracking
®
Filter Systems
Char t B - Nominal Voltage Codes
(substitute for “xxx” to complete model number)
Single Phase, 2 wire plus ground
100, 110, 120, 230, 240, 277, 346, 400, 480, 600
Split Single Phase, 3 wire plus ground
100/173, 110/190, 120/208 or 240, 230/400, 277/480, 346/600
Three Phase Delta, 3 wire plus ground
208, 240, 380, 400, 480, 600
Three Phase Delta Hi-Leg, 4 wire plus ground
120/240
Three Phase Wye, 3 or 4 wire plus ground
100/173, 110/190, 120/208, 230/400, *277/480, 346/600
A
D
F
E
B
- Diameter
C
- Optional Features
   2.0” MAX
- Standard Features
   .50” MAX
Line Frequency 
47 to 63 Hz
Line Voltage
±15% nominal
Temperature 
-40 to +60°C
Operating Humidity 
0 to 95% noncondensing
Altitude 
0 to 18,000 feet
Audible Noise
Less than 45 dBa
Operational Crest Factor  3.0
Warranty
10-Years Parts and 
5-Years On-Site Labor
Monitoring 
Options
Standard Features Include:
•Audible Alarm, 
Transient Counter
• Door LEDs indicating
unit status
• Individual Module
Status LEDs, and
-06
Form C Dry Contacts
for Remote System
Integrity Monitoring
and Indication of
Under Voltage, Phase
and/or Power Loss.
Optional Features Include:
• Additional Seven-
Digit Transient Counter
for Normal Mode
-03
• Additional Form C
Dry Contacts
NOTES: For configurations not
mentioned, including caseless
units for switchgear applications
and ungrounded delta units, 
consult factory. For different levels 
of surge current capacity mode
and/or phase, consult factory.
CODE: 
L - N = Line to Neutral
L - G = Line to Ground
N - G = Neutral to Ground
L - L = Line to Line
*Valid for 220/380 and 
240/415 per IEC.
Example Model Number:
F120Y30-03