Falcon F3400 Manuel D’Utilisation

Page de 94
www.rletech.com
80
970.484.6510
A
  Analog Input 4-20mA Reference Chart
CT20
Current
0 - 30 Amps
0 - 60 Amps
0 - 120 Amps
7
15
30
-7
-15
-30
CT200
Current
0 - 20 Amps
0 - 200 Amps
5
50
-5
-50
CT300
Current
0 - 100 Amps
0 - 300 Amps 
25
75
-25
-75
VOLTAGE
PT300 
Voltage - Single Phase
0 - 300 VAC
75 
-75
3PT300
Voltage - Three Phase
0 - 300 VAC
75 
-75
PT600
Voltage - Single Phase
0 - 600 VAC
150
-150
3PT600
Voltage - Three Phase
0 - 600 VAC 
150
-150
LD5100 4-20mA
LD5100
Leak Detection
4-20mA Output (Calc. in ft/m)
0 - 1000ft / 305m
250
-250
0 - 2500ft / 762m
625
-625
0 - 5000ft / 1524m
1250
-1250
LD5000 4-20mA
LD5000
Leak Detection
4-20mA Output (Calc. in ft/m)
0 - 500ft / 152m
143
-179
0 - 1000ft / 305m
286 
-357
0 - 1500ft / 457m 
429
-536
0 - 2000ft / 610m
571
-714
0 - 2500ft / 762m
714
-893
0 - 3000ft / 914m
857
-1071
0 - 3500ft / 1067m
1000
-1250
0 - 4000ft / 1219m 
1143
-1429
0 - 4500ft / 1372m
1286
-1607
0 - 5000ft / 1524m
1429
-1786
Table A.1 Analog Input 4-20mA Reference Chart (continued)
RLE 
Product 
Number
Transducer Type
Range
Gain
Offset