RuggedCom RS910L Manuel D’Utilisation

Page de 29
17 
 
2007 RuggedCom Inc. All rights reserved 
 
Rev100
 
 
 
Figure 12: Conceptual recommended RS485 wiring diagram 
 
3.1.5  Serial Port Transient Protection 
 
RuggedCom does not recommend the use of copper cabling of any length for critical real-time 
substation automation applications. However, transient suppression circuitry is present on all 
copper ports to protect against damage from electrical transients and to ensure IEC 61850-3 and 
IEEE 1613 Class 1 conformance. This means that during the transient event communications 
errors or interruptions may occur but recovery is automatic. RuggedCom also does not recommend 
to use these ports to interface to field devices across distances which could produce high levels of 
ground potential rise, (i.e. greater than 2500V) during line to ground fault conditions.