UPS Manual Test
Manual UPS and Battery tests may be performed from the UPS configuration screen.
Tests may be performed when the battery is not being charged.
To run the battery test scroll to the “Manual Bat Test” parameter press the Enter
button twice.
** Note: In order for the UPS to operate normally, Manual Bypass should always be
set to OFF because the load will not be protected by the unit when Manual Bypass is
ON.
*** Note: Turn off the UPS and keep the AC power on to use the Generator function.
(go to normal mode for \Generator\OFF).
5.5  Interpreting UPS Messages
Troubleshooting procedures described here provide instructions to be used to isolate
UPS malfunctions.
Start the troubleshooting procedure in the event of a control panel alarm.
Audible Alarms
•  While operating on battery power (ON BAT LED is on) the UPS will beep once
at 5-second intervals.
•  While operating on battery power and the battery power is low (ON BAT LED is
flashing) the UPS will beep twice at 5-second intervals.
•  In the event of an internal fault with an active alarm (ALARM LED is on), the
UPS will provide a constant audible alarm and display an error message on the
LCD display.
•  While operating in the Bypass mode (BYPASS LED is on) the UPS will not
beep.
Silencing an Alarm
With the exception of a LOW BATTERY Alarm, pressing any of the front panel
buttons will turn off the alarm. Select Silent Alarm Mode to disable all audible
alarms.