ADC Power Distribution Products Manuel D’Utilisation

Page de 40
ADCP-80-526 • Issue 6 • December 2006
Page 21
© 2006, ADC Telecommunications, Inc.
4.4
Connecting Alarms
Depending on the model being installed, the fuse platform will have either of two types of alarm
connectors on the rear side of the platform:
• Screw-down barrier terminal strip
• Wire wrap pin
 shows the two types. Connect the connectors as follows: 
Screw-down barrier terminal strip: The terminal screw size is 3-48. Terminate wire leads
with crimp-on spade lug or ring connectors that have a maximum width of 0.200 (5.080
mm) or use #16 to #30 AWG copper wire without lugs (insulation stripped back). In
selecting wire size, follow local code referring to the ampacity guidelines provided in
Appendix A of this manual.Tighten the terminal screws to approximately 9 pound-inches
(1 Newton-meter) of force.
Wire-wrap terminal: Wrap terminal block pins using #22 to #26 AWG copper wire with
insulation stripped back. In selecting wire size, follow local code referring to the ampacity
guidelines provided in Appendix A of this manual.
Figure 16.  Alarm Contact Connections 
SCREW-DOWN BARRIER TERMINAL STRIP
WIRE-WRAP PIN TERMINAL BLOCK
17056-A
CONNECT TO  CORRESPONDING
ALARM CONNECTORS
CONNECT TO REMOTE ALARMS
CONNECT TO REMOTE ALARMS
CONNECT TO  CORRESPONDING
ALARM CONNECTORS
CONNECT TO AUDIO ALARMS
CONNECT TO VISUAL  ALARMS
CONNECT TO REMOTE ALARMS