Installation and Configuration
15
6.3.2 Input & Output Terminal Block Connections
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not 
share the same conduit.
For best performance, distribute all L-N loads evenly between L1 and L2.
Table 1
Electrical requirements
Input Current
Rating
Recommended (Max.) External
Overcurrent Protection
Recommended Wire
(including ground wire)
(75°C copper wire)
Maximum Wire
Accepted by
Terminal Block
Terminal
Tightening
Torque
48A
60A
6 AWG
4 AWG
22 in-lb 
(2.48N-m)
NOTE
1. The installer must provide circuit breaker protection according to local codes. The utility 
disconnect should be within sight of the UPS or have an appropriate lock-out. Maintain 
service space around the UPS or use flexible conduit.
2. The installer must provide output distribution panels, circuit breaker protection or 
emergency disconnects according to local codes. Output circuits must not share a common 
conduit with any other wiring.
OUTPUT
INPUT
60A Max. Branch
Overcurrent Protection
6 AWG - USE COPPER WIRE ONLY - 22 in-lb (2.48N-m)- Strip 8mm
0
120
2
08 o
r 2
40
Output to Load - See Note 1
0
2
08 o
r 2
40
Input to UPS - See Note 2