Emerson UPS Systems Manuel D’Utilisation

Page de 36
Installation Drawings
22
Figure 15 Liebert NXL Maintenance Bypass Cabinet Control wire diagram without interlock
WIRE DIAGRAM WITHOUT INTERLOCK
  LOW VOLTAGE
TERMINAL STRIP
         - TB1 -
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
EPO PB SW
TB1-1
TB1-2
TB1-4
TB1-5
TB1-6
TB1-7
TB1-8
TB1-9
TB1-10
TB1-11
TB1-12
TB1-13
TB1-3
Connections at UPS External
Interface Board (EIB)
TB0823
TB0813
TB0811
TB0821
02-806708
1
3
TB0821
1
3
1
3
TB0811
TB0813
1
3
TB0824
Table 4
Control wiring connections without 
interlock
From
To
Purpose
TB1-1
Customer EPO
Push Button Switch
EPO Signal
TB1-2
Customer EPO
Push Button Switch
TB1-3
TB0821-2
Maint. Bypass Enable
Contacts
TB1-4
TB0821-1
TB1-5
TB0824-3
UPS REPO Contacts
TB1-6
TB0824-2
TB1-7
TB0824-1
TB1-8
TB0811-3
MIB Contacts
TB1-9
TB0811-2
TB1-10
TB0811-1
TB1-11
TB0813-3
MBB Contacts
TB1-12
TB0813-2
TB1-13
TB0813-1