Emerson MODBUS 485 Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
113
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
Source 2 Overload
—
40290
1
—
Bit 3
Power Supply 2 Fault
—
40290
1
—
Bit 4
Frequency Deviation
—
40290
1
—
Bit 5
Transfer Inhibit
—
40290
1
—
Bit 6
Auto Retransfer Primed
—
40290
1
—
Bit 7
Out of Synchronization
—
40290
1
—
Bit 8
Source 1 Failure
—
40290
1
—
Bit 9
Source 2 Failure
—
40290
1
—
Bit 10
Auto Retransfer Failed
—
40291
1
—
Bit 0
Overload
—
40291
1
—
Bit 1
Control Fuse 1 Blown
—
40291
1
—
Bit 2
Control Fuse 2 Blown
—
40291
1
—
Bit 3
Source 1 CB1 Open
—
40291
1
—
Bit 4
Source 2 CB2 Open
—
40291
1
—
Bit 5
Output CB3 Open
—
40291
1
—
Bit 6
Custom Alarm 1
—
40291
1
—
Bit 7
Custom Alarm 2
—
40291
1
—
Bit 8
Bypass CB4 Closed
—
40291
1
—
Bit 9
Bypass CB5 Closed
—
40291
1
—
Bit 10
Custom Alarm 3
—
40292
1
—
Bit 0
Custom Alarm 4
—
40292
1
—
Bit 1
Custom Alarm 5
—
40292
1
—
Bit 2
Custom Alarm 6
—
40292
1
—
Bit 3
Custom Alarm 7
—
40292
1
—
Bit 4
Custom Alarm 8
—
40292
1
—
Bit 5
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 38
Liebert STS
™
, Liebert STS/PDU
™
- Input and Holding - STS (continued)
Controller
STS
Liebert Products
Liebert STS
Liebert STS/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units