Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - Power Distribution and Power Conditioning Products
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
116
Internal Comm Fail
40290
1
Bit 5
External Comm Fail
40290
1
Bit 6
CB1 Shunt Trip Fail
40290
1
Bit 7
CB2 Shunt Trip Fail
40290
1
Bit 8
CB6 Neutral Open
40290
1
Bit 9 (N/A to 4P)
Contactor Neutral Fail
40290
1
Bit 10 (N/A to 4P)
Heatsink Overtemp
40290
1
Bit 11
Equipment Overtemp
40290
1
Bit 12 (N/A to 4P)
Ambient Overtemp
40290
1
Bit 13 (N/A to 4P)
S1 Undervolts
40290
1
Bit 14
S1 Undervolts (RMS)
40290
1
Bit 15
S1 Overvolts
40291
1
Bit 0
S1 Over/Under Freq
40291
1
Bit 1
S1 Fail
40291
1
Bit 2
S2 Undervolts
40291
1
Bit 3
S2 Undervolts (RMS)
40291
1
Bit 4
S2 Overvolts
40291
1
Bit 5
S2 Over/Under Frequency
40291
1
Bit 6
S2 Fail
40291
1
Bit 7
S1 Overcurrent
40291
1
Bit 8
S2 Overcurrent
40291
1
Bit 9
S1 I-Peak
40291
1
Bit 10
S2 I-Peak
40291
1
Bit 11
Sources Out of Sync
40291
1
Bit 12
Load On Alternate Source
40291
1
Bit 13
Auto Retransfer Inhibit
40291
1
Bit 14
CB1 (S1) Open
40292
1
Bit 0
CB2 (S2) Open
40292
1
Bit 1
CB4 (S1 BYP) Closed
40292
1
Bit 2
CB5 (S2 BYP) Closed
40292
1
Bit 3
CB3 Output Bkr Open
40292
1
Bit 4
CB3A Output Bkr Open
40292
1
Bit 5
S1 Phase Rotation Error
40292
1
Bit 6
S2 Phase Rotation Error
40292
1
Bit 7
Transfer Inhibited
40292
1
Bit 8
Output Undervoltage
40292
1
Bit 9
History Logs Full
40292
1
Bit 10
Equipment Fan Fail
40292
1
Bit 11
Load Volt THD High
40292
1
Bit 12
Table 39
Liebert STS2
, Liebert STS2/PDU
 - Input and Holding - STS2 (continued)
Controller
STS2
Liebert Products
Liebert STS2
Liebert STS2/PDU
Available Points
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale 
Notes / Units