Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
143
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Table 53
Liebert NX
 - Input and Holding
Data Description
Input
Register
Holding
Register
# of
Reg.
Scale
Notes / Units
Number of Input Lines
30004
40004
1
Bits 12 - 15
Number of Bypass Lines
30004
40004
1
Bits 4 - 7
Number of Output Lines
30004
40004
1
Bits 8 - 11
Number of SubModules
30009
40009
1
Module Number
30014
40014
1
Device Module Count
30015
40015
1
Device Redundant Count
30016
40016
1
Device Module Mode
30017
40017
1
Nominal Power Rating
30021
40021
2
VA
Nominal Input Voltage
30027
40027
1
V
Nominal Output Voltage
30028
40028
1
V
Nominal Static Bypass Switch Voltage
30029
40029
1
V
Nominal Input Frequency
30031
40031
1
10
Hz
Nominal Output Frequency
30032
40032
1
10
Hz
Nominal Power Factor
30033
40033
1
100
Nominal DC Bus #1 Voltage
30035
40035
1
V
Nominal DC Bus #2 Voltage
30036
40036
1
Nominal Battery Float Voltage
30038
40038
1
V
Load Bus Sync Mode
30040
40040
1
Auto Restart Delay
30051
40051
1
Seconds
Device Low Battery Time
30053
40053
1
Minutes
Input Frequency
30107
1
10
Hz
Output Frequency
30108
1
10
Hz
Bypass Frequency
30109
1
10
Hz
Battery Charge Status
30112
1
1 - 100% Charged
2 - Less than 100% Charged
3 - Charging
4 - Discharging
5 - Float Charging
6 - Equalize Charging
Battery Voltage
30113
1
V
Battery Current (Charge/Discharge)
30114
1
A
Battery Time Remaining
30115
1
Minutes
Battery Charge Percentage
30116
1
%
Battery Temperature
30117
1
C
Ambient Temperature
30119
1
C
Parallel Load Source
30128
1
Rotary Breaker
30129
1
Battery Test Result
30130
1
1 - Unknown
2 - Passed
3 - Failed
4 - In Progress
5 - System Failure
6 - Inhibited
Input Voltage L1-L2
30151
1
V
Input Voltage L1
30153
1
V