Emerson MODBUS 485 Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
166
Multiple Fan Failure
Multiple fan failure
On Generator
A generator is supplying the power to the system
Output Amp Over User Limit-Phs A
The phase A output has exceeded the user amperage threshold
Output Amp Over User Limit-Phs B
The phase B output has exceeded the user amperage threshold
Output Amp Over User Limit-Phs C
The phase C output has exceeded the user amperage threshold
Output Apparent Power Rating
Output apparent power rating
Output Breaker (CB2/IOB)
Output breaker (CB2/IOB)
Output Load on Maint. Bypass
The output power is supplied by the maintenance bypass
Output Qualification Status
output qualification status
Output Real Power Rating
Output real power rating
Output Series Static Switch
output series static switch
Output Wire Configuration
Output wire configuration
Power Supply Failure
Power supply failure
Rectifier Active Filter
Rectifier input active filter configuration
Rectifier Failure
Rectifier failure - rectifier is off
Rectifier Feed Breaker (RFB)
Rectifier feed breaker (RFB)
Rectifier Input Passive Filter
Rectifier input passive filter configuration
Rectifier Operation Inhibit-Ext
The operation of the rectifier is inhibited by an external signal
Rectifier Passive Filter Switch
Rectifier input passive filter switch configuration
Rectifier Pulse Count
Rectifier pulse count per cycle configuration
Rectifier Status
rectifier status
SBS Load Disconnect
SBS load disconnect
Service Code Active
Service code is running
Static Bypass Switch
Static Bypass Switch state - On/Off
Static Switch Type
Static switch type configuration
System Breaker(s) Close Failure
One or more breakers in the system failed to close
System Breaker(s) Open Failure
One or more breakers in the system failed to open
System Controller Error
System controller internal error
System Date and Time
The system date and time
System Fan Failure - Redundant
Redundant system fan failure
System Input Current Imbalance
System Input Currents are Imbalanced
System Input Current Limit
The RMS input current has reached the input current limit threshold
System Input Frequency
The system input frequency
System Input Nominal Frequency
The nominal (or rated) system input frequency
System Input Nominal Voltage
The nominal (or rated) system input voltage
System Input Phs Rotation Error
The power conductors on the input line are not wired to the UPS in the
sequence preferred for the rectifier (A-B-C)
System Input Power Problem
The input is not qualified to provide power to the system
System Input Power Source
System input power source
System Input RMS A-B
The System Input RMS Voltage between Phase A and Phase B
System Input RMS B-C
The System Input RMS Voltage between Phase B and Phase C
System Input RMS C-A
The System Input RMS Voltage between Phase C and Phase A
System Input RMS Current Phase A
The system input RMS current for Phase A
System Input RMS Current Phase B
The system input RMS current for Phase B
Table 57
Liebert NXL
™
- 60Hz, UL version (Model 40) - Glossary (continued)
Data Label
Data Description