Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
166
Multiple Fan Failure 
Multiple fan failure 
On Generator 
A generator is supplying the power to the system 
Output Amp Over User Limit-Phs A 
The phase A output has exceeded the user amperage threshold 
Output Amp Over User Limit-Phs B 
The phase B output has exceeded the user amperage threshold 
Output Amp Over User Limit-Phs C 
The phase C output has exceeded the user amperage threshold 
Output Apparent Power Rating 
Output apparent power rating 
Output Breaker (CB2/IOB) 
Output breaker (CB2/IOB) 
Output Load on Maint. Bypass 
The output power is supplied by the maintenance bypass 
Output Qualification Status 
output qualification status 
Output Real Power Rating 
Output real power rating 
Output Series Static Switch 
output series static switch 
Output Wire Configuration 
Output wire configuration 
Power Supply Failure 
Power supply failure 
Rectifier Active Filter 
Rectifier input active filter configuration 
Rectifier Failure 
Rectifier failure - rectifier is off 
Rectifier Feed Breaker (RFB) 
Rectifier feed breaker (RFB) 
Rectifier Input Passive Filter 
Rectifier input passive filter configuration 
Rectifier Operation Inhibit-Ext 
The operation of the rectifier is inhibited by an external signal 
Rectifier Passive Filter Switch 
Rectifier input passive filter switch configuration 
Rectifier Pulse Count 
Rectifier pulse count per cycle configuration 
Rectifier Status 
rectifier status
SBS Load Disconnect 
SBS load disconnect 
Service Code Active 
Service code is running 
Static Bypass Switch 
Static Bypass Switch state - On/Off 
Static Switch Type 
Static switch type configuration 
System Breaker(s) Close Failure 
One or more breakers in the system failed to close 
System Breaker(s) Open Failure 
One or more breakers in the system failed to open 
System Controller Error 
System controller internal error 
System Date and Time 
The system date and time 
System Fan Failure - Redundant 
Redundant system fan failure 
System Input Current Imbalance 
System Input Currents are Imbalanced 
System Input Current Limit 
The RMS input current has reached the input current limit threshold 
System Input Frequency 
The system input frequency 
System Input Nominal Frequency 
The nominal (or rated) system input frequency 
System Input Nominal Voltage 
The nominal (or rated) system input voltage 
System Input Phs Rotation Error 
The power conductors on the input line are not wired to the UPS in the 
sequence preferred for the rectifier (A-B-C) 
System Input Power Problem 
The input is not qualified to provide power to the system 
System Input Power Source 
System input power source 
System Input RMS A-B 
The System Input RMS Voltage between Phase A and Phase B 
System Input RMS B-C 
The System Input RMS Voltage between Phase B and Phase C 
System Input RMS C-A 
The System Input RMS Voltage between Phase C and Phase A 
System Input RMS Current Phase A 
The system input RMS current for Phase A 
System Input RMS Current Phase B 
The system input RMS current for Phase B 
Table 57
Liebert NXL
 - 60Hz, UL version (Model 40) - Glossary (continued)
Data Label
Data Description