Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
196
Bypass Current L2
30210
1
A
Output Voltage L2
30213
1
V
Output Current L2
30214
1
A
Input Voltage L3
30253
1
V
Input Current L3
30254
1
A
Bypass Voltage L3
30259
1
V
Bypass Current L3
30260
1
A
Output Voltage L3
30263
1
V
Output Current L3
30264
1
A
Black Out Count
30301
1
Brown Out Count
30302
1
Transient Count
30301
1
Silent Audible Alarm
40101
Any value
Battery Start
40102
1
1=Start, 0=Abort
Open UPS Output Switch
40104
Delay time in Seconds, last digit will be 
ignored
Reboot UPS Output Switch
40105
1
Delay time in Seconds, last digit will be 
ignored
Close UPS Output Switch
40106
Delay time in Seconds, last digit will be 
ignored
Transfer Load to Bypass
40107
1
Any value
Transfer Load to Inverter
40108
Any value
Reset UPS Statistic data
40111
1
Any value
Turn UPS Outlets On
40112
1
Bitmap mask for Outlet 1-16. All bits set to 1 
will be turned On
Turn UPS Outlets Off
40113
1
Bitmap mask for Outlet 1-16. All bits set to 1 
will be turned Off
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.
Table 66
Liebert Series 300
 UPS - Input and Holding (continued)