Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
233
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Remote Sensor Average 
Temperature
Analog_Value
314
5007_1
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor Average 
Temperature
Analog_Value
10314
5007_1_deg_F
RD
Units: deg F
2, 3, 4, 
5, 6
Remote Sensor Maximum 
Temperature
Analog_Value
315
5006_1
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor Maximum 
Temperature
Analog_Value
10315
5006_1_deg_F
RD
Units: deg F
2, 3, 4, 
5, 6
Remote Sensor System 
Average Temperature
Analog_Value
316
5591_1
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor System 
Average Temperature
Analog_Value
10316
5591_1_deg_F
RD
Units: deg F
2, 3, 4, 
5, 6
Remote Sensor System 
Maximum Temperature
Analog_Value
317
5592_1
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor System 
Maximum Temperature
Analog_Value
10317
5592_1_deg_F
RD
Units: deg F
2, 3, 4, 
5, 6
Remote Sensors - Remote Sensor 1
Remote Sensor Temperature
Analog_Value
329
5059_1_1
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor Temperature
Analog_Value
10329
5059_1_1_deg
_F
RD
Units: deg F
2, 3, 4, 
5, 6
Remote Sensors - Remote Sensor 2
Remote Sensor Temperature
Analog_Value
341
5059_1_2
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor Temperature
Analog_Value
10341
5059_1_2_deg
_F
RD
Units: deg F
2, 3, 4, 
5, 6
Remote Sensors - Remote Sensor 10
Remote Sensor Temperature
Analog_Value
437
5059_1_10
RD
Units: deg C
2, 3, 4, 
5, 6
Remote Sensor Temperature
Analog_Value
10437
5059_1_10_de
g_F
RD
Units: deg F
2, 3, 4, 
5, 6
Static Pressure
Static Pressure Set Point
Analog_Value
461
5626_1
RW
Units: Pa
3, 6
Unit Static Pressure
Analog_Value
462
5627_1
RD
Units: Pa
3, 6
System Static Pressure
Analog_Value
463
5628_1
RD
Units: Pa
3, 6
EconoPhase - Pump 1
Pump Hours
Analog_Value
523
5298_1_1
RW
Units: hr
5
EconoPhase - Pump 2
Pump Hours
Analog_Value
526
5298_1_2
RW
Units: hr
5
Global Condensers - GC Low Noise Mode
Condenser Low Noise Mode 
Max Fan Speed
Analog_Value
529
5548_1_1
RW
Units: %
3, 4, 5, 
6
Condenser Normal Mode Max 
Fan Speed
Analog_Value
530
5549_1_1
RW
Units: %
3, 4, 5, 
6
Condenser Low Noise Mode 
Start Time
Analog_Value
531
5552_1_1
RW
Units: Seconds 
since Midnight
3, 4, 5, 
6
Condenser Low Noise Mode 
Stop Time
Analog_Value
532
5553_1_1
RW
Units: Seconds 
since Midnight
3, 4, 5, 
6
Table 78
Liebert Challenger 3000
, Liebert Challenger ITR
, Liebert CW
, Liebert Deluxe System/3
Liebert DS
, Liebert DSE
, Liebert HPM
, Liebert PeX
 - Analog Data (continued)
Data Label
Object Type
Instanc
e
Object  Name
Acces
s
Notes
Extra 
Notes