Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - Thermal Management Products
289
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
Smoke Detected - Event Type
Multistate_Value
859
4722_1
RW
1 = Message
2 = Warning
3 = Alarm
Water Under Floor - Event Control
Multistate_Value
860
4724_1
RW
1 = Disabled
2 = Enabled
Water Under Floor - Event Type
Multistate_Value
861
4725_1
RW
1 = Message
2 = Warning
3 = Alarm
Service Required - Event Control
Multistate_Value
862
4727_1
RW
1 = Disabled
2 = Enabled
Service Required - Event Type
Multistate_Value
863
4728_1
RW
1 = Message
2 = Warning
3 = Alarm
Fan Issue - Event Control
Multistate_Value
864
4730_1
RW
1 = Disabled
2 = Enabled
Fan Issue - Event Type
Multistate_Value
865
4731_1
RW
1 = Message
2 = Warning
3 = Alarm
System Events
System Event Acknowledge/Reset
Multistate_Value
876
4717_1
WO
1 = Reset
2 = Acknowledge
Table 94
Liebert XDP
, Liebert XDC
 - Multistate Data (continued)
Controller Liebert iCOM
®
 v4
Data Label
Object Type
Instance
Object
Name
Access
Notes