Emerson MODBUS 485 Manuel D’Utilisation
BACnet Communications - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
332
MMS Module Inverter Status MultiState_Value
276
4858_8
RD
1 = off
2 = on
1+N
MMS Module Output Voltage
Status
MultiState_Value
277
4859_8
RD
1 = Fail
2 = Marginal Low
3 = Normal
4 = Marginal High
1+N, SCC
MMS Module Output Source MultiState_Value
278
4860_8
RD
1 = off
2 = Normal
3 = Bypass
4 = Maintenance
Bypass
1+N, SCC
Intelligent Paralleling
Intelligent Parallel Operation
Intelligent Parallel Operation
State
MultiState_Value
289
5448_1
RD
1 = disabled
2 = enabled
1+N, N+1,
SCC
Intelligent Parallel Mode
MultiState_Value
290
5449_1
RD
1 = Idle (Fast
Recovery)
2 = Disconnect (More
Efficient)
3 = off (Most Efficient)
1+N, N+1,
SCC
ECO Mode
ECO Mode Operation State
MultiState_Value
301
5454_1
RW
1 = disabled
2 = enabled
SMS, 1+N,
SCC
Continuous Operation - ECO
Mode
MultiState_Value
302
5455_1
RD
1 = disabled
2 = enabled
SMS, 1+N,
SCC
ECO Mode - EcoModeSchedule 1
Schedule Operation State -
Schedule Operation State -
ECO Mode
MultiState_Value
313
5461_1_1
RD
1 = disabled
2 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode MultiState_Value
314
5462_1_1
RD
1 = stop
2 = start
SMS, 1+N,
SCC
ECO Mode - EcoModeSchedule 2
Schedule Operation State -
Schedule Operation State -
ECO Mode
MultiState_Value
326
5461_1_2
RD
1 = disabled
2 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode MultiState_Value
327
5462_1_2
RD
1 = stop
2 = start
SMS, 1+N,
SCC
Schedule Day of Week -
ECO Mode
MultiState_Value
328
5463_1_2
RD
1 = Unknown
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
8 = Sunday
SMS, 1+N,
SCC
ECO Mode - EcoModeSchedule 16
Schedule Operation State -
Schedule Operation State -
ECO Mode
MultiState_Value
508
5461_1_16
RD
1 = disabled
2 = enabled
SMS, 1+N,
SCC
Schedule Action - ECO Mode MultiState_Value
509
5462_1_16
RD
1 = stop
2 = start
SMS, 1+N,
SCC
Schedule Day of Week -
ECO Mode
MultiState_Value
510
5463_1_16
RD
1 = Unknown
2 = Monday
3 = Tuesday
4 = Wednesday
5 = Thursday
6 = Friday
7 = Saturday
8 = Sunday
SMS, 1+N,
SCC
Table 108 Liebert NXL
™
- 60Hz, UL version (Model 40) - Multistate Data (continued)
Data Label
Object
Type
Instance
Object
Name
Access
Notes
Liebert
NXL Type