Emerson MODBUS 485 Manuel D’Utilisation

Page de 372
BACnet Communications - UPS Systems
349
Liebert
®
 IntelliSlot
®
 Modbus/BACnet IP
System
UPS Module Type
MultiState_Value
87
4303_1
RD
1 = Single 
Module System
2 = Module (1 + 
1)
3 = Module (1 + 
N)
4 = Module (N + 
1)
5 = System 
Control Cabinet
6 = Main Static 
Switch
Bypass Input Wire Configuration
MultiState_Value
88
4304_1
RD
1 = Two Wire 
(single phase + 
return)
2 = Two Wire (2 
phase, no 
neutral)
3 = Three Wire (2 
phase + neutral)
4 = Three Wire (3 
phase, no 
neutral)
5 = Four Wire (3 
phases + neutral)
Output Wire Configuration
MultiState_Value
89
4305_1
RD
1 = Two Wire 
(single phase + 
return)
2 = Two Wire (2 
phase, no 
neutral)
3 = Three Wire (2 
phase + neutral)
4 = Three Wire (3 
phase, no 
neutral)
5 = Four Wire (3 
phases + neutral)
Static Switch Type
MultiState_Value
90
4306_1
RD
1 = Not 
Applicable
2 = Continuous 
Duty
3 = Momentary 
Duty
Table 112 Liebert NXL
 - 50 Hz, CE version (Models 48 and 49)—Multistate Data
Data Label
Object Type
Instance
Object Name
Access
Notes