Emerson MODBUS 485 Manuel D’Utilisation
Modbus 485 and Modbus IP Protocols - UPS Systems
Liebert
®
IntelliSlot
®
Modbus/BACnet IP
192
Table 63
Liebert PowerSure
™
Interactive 2 - Status and Coil
Applies only to PSI units manufactured before June 1, 2008 (Julian date 08153)
Data Description
Status
Coil
Number
of Bits
Scale
Notes / Units
Audible Alarm Enabled
10002
2
1
—
—
Automatic Battery Test Enabled
10003
3
1
—
—
DC-To-DC Converter On
10042
—
1
—
—
Battery Charger On
10044
—
1
—
—
Load Circuit 1 State
10057
—
1
—
—
Load Circuit 2 State
10058
—
1
—
—
Load Circuit 3 State
10059
—
1
—
—
Load Circuit 4 State
10060
—
1
—
—
Load Circuit 5 State
10061
—
1
—
—
Load Circuit 6 State
10062
—
1
—
—
Load Circuit 7 State
10063
—
1
—
—
Load Circuit 9 State
10065
—
1
—
—
Load Circuit 10 State
10066
—
1
—
—
Load Circuit 11 State
10067
—
1
—
—
Load Circuit 12 State
10068
—
1
—
—
Load Circuit 13 State
10069
—
1
—
—
Load Circuit 14 State
10070
—
1
—
—
Load Circuit 15 State
10071
—
1
—
—
Load Circuit 16 State
10072
—
1
—
—
Load On Inverter
10073
—
1
—
—
Boost Mode On
10075
—
1
—
—
Buck Mode On
10076
—
1
—
—
Replace Battery
10081
—
1
—
—
Battery Under Test
10082
—
1
—
—
Shutdown Reason - Over Temperature
10086
—
1
—
—
Shutdown Reason - Overload
10087
—
1
—
—
Shutdown Reason - Output Short
10089
—
1
—
—
Shutdown Reason - Line Neutral Swap
10090
—
1
—
—
Shutdown Reason - Low Battery
10092
—
1
—
—
Shutdown Reason - Remote Shutdown
10093
—
1
—
—
Shutdown Reason - Input Under Voltage
10094
—
1
—
—
Shutdown Reason - Hardware
10096
—
1
—
—
Load On Battery
10128
—
1
—
—
Output Off Pending
10151
—
1
—
—
Low Battery - Shutdown Imminent
10152
—
1
—
—
Output Overload
10154
—
1
—
—
Over Temperature Warning
10171
—
1
—
—
Input Power Supply Fail
10186
—
1
—
—
Input Over Voltage
10187
—
1
—
—
Input Under Voltage
10188
—
1
—
—
Input BrownOut
10189
—
1
—
—
Bad Input Frequency
10190
—
1
—
—
Output Under Voltage
10218
—
1
—
—
Output Over Voltage
10219
—
1
—
—
Charger Failed
10234
—
1
—
—
Battery Under Voltage
10241
—
1
—
—
Battery Over Voltage
10242
—
1
—
—
If the Scale column has a value for a Data Description, divide the Modbus value by the value in the Scale column to get the scaled value.