GE AF-300 Manuel D’Utilisation
-22-
Classifi-
cation
Termi-
nal
nal
symbol
Terminal name
Detailed specifications
Remarks
Analog
output
FM, 11 Analog monitor
Data selected between the following items is
output with DC voltage:
output with DC voltage:
Output frequency
PID feedback value
Output current
DC link circuit voltage
PID feedback value
Output current
DC link circuit voltage
* Up to two analog voltmeters (input imped-
ance : 10 k
ance : 10 k
Ω
can be connected.
Note: Output waveform: An AC pulse is out-
put with consistent frequency and variable
duty. The average DC voltage is proportional
to output frequency and output current (fre-
quency : 121.6 Hz).
put with consistent frequency and variable
duty. The average DC voltage is proportional
to output frequency and output current (fre-
quency : 121.6 Hz).
Contact
output
30A
30B
30C
30B
30C
Alarm output for any
fault
fault
If the drive is stopped with an alarm, the
non-voltage contact signal (SPDT) is output
non-voltage contact signal (SPDT) is output
(Contact rating: 250V ac, 0.3 A, Power factor
= 0.3)
(48V dc, 0.5A for Low-voltage Directive or
42V dc, 0.5A for UL/cUL)
= 0.3)
(48V dc, 0.5A for Low-voltage Directive or
42V dc, 0.5A for UL/cUL)
Whether an alarm is generated with an excit-
ing operation or non-exciting operation can
be switched.
ing operation or non-exciting operation can
be switched.
Optional
DX
+
DX
−
RS485 RTU commu-
nication input/output
nication input/output
Terminal for RS485 communication (when
option board is installed)
option board is installed)
DX
+
: Non-inverted signal,
DX
−
: Inverted signal
Installed on op-
tional board.
tional board.