24      Chapter 3  Electrical Installation 
HIPULSE U UPS Single Module And “1+N” (Expandable) 160/200/300/400kVA    User Manual 
Table 3-8    Description of auxiliary terminal block X3 
X3 terminal reference 
Reference label 
Description 
FB 
BCB normally open auxiliary contact 
2 GND 
Signal 
ground 
3 OL 
Cable 
detection 
4 +12V 
Power 
positive 
5 TMP_T 
Temperature 
sensing 
terminal 
GND 
Temperature sensing signal ground 
7 LM355+ 
LM335 
detection 
positive 
8 LM355+GND 
LM335 
signal 
ground 
9 DRV 
BCB 
drive 
10 DRV_GND 
Drive 
ground 
Note:  
1. The auxiliary cables of the battery must be screened and double insulated. 
2. The screen is connected to the earth of the battery cabinet or supporting rack. 
3. Use multiple-core shielded cables with a section of 0.5 to 1 mm
2
4. Connect the cables with the fast-on 6.3*0.8 mm terminals (female) 
 
Connect the BCB control and temperature compensation cables between the UPS auxiliary terminal block X3 and 
BCB control board. For details, refer to Figure 6-5. These cable must be shielded, shield should be connected at 
protective earth of battery cabinet or battery breaker, not of UPS. 
  Note 
If battery temperature compensation is needed, this function must be activated by the commissioning engineer. 
 
3.4   Connecting Main Cabinet And Side Cabinet 
The 300kVA UPS (12-pulse rectifier) and 400kVA UPS comprise a main cabinet and a side cabinet.. In installation, 
you need to make electrical connection between the main cabinet and side cabinet.   
3.4.1   Connecting Power Cables 
The power cable connections between the main cabinet and side cabinet of the 300kVA UPS (12-pulse rectifier) and 
400kVA UPS are shown in Figure 3-9 to Figure 3-11. The installation engineer should make cable connection in strict 
accordance with these figures.   
A
W4-2, W5-2, W6-2
W4-2
W5-2
W6-2
Side cabinet
Main cabinet
Nut M10
Spring w asher 10
Plain w asher 10
Bolt M10 *35
A amplified view
 
Figure 3-9    Power cable connection between main cabinet and side cabinet of 300kVA UPS (12-pulse rectifier)