Emerson P/N MMI-20019808 Manuel D’Utilisation

Page de 78
 
52
Micro Motion EtherNet/IP Module
Device Profile
B.5
Data types
B.6
Codes and integer values
Table B-6  Data types
Data type
Size (bytes)
Description
Range
BOOL
1
True/false represented as 0 = false and 1 = 
true
0, 1
SINT
1
8-bit signed integer
–128 to +127
USINT
1
8-bit unsigned integer
0 to 255
INT
2
16-bit signed integer
–32768 to +32767
UINT
2
16-bit unsigned integer
0 to 65535
DINT
4
32-bit signed integer
–2147483648 to +2147483647
UDINT
4
32-bit unsigned integer
0 to 4294967296
REAL
4
IEEE single-precision floating-point
–3.8E38 to +3.8E38
DREAL
8
IEEE double-precision floating-point
ENGUNITS
1
Enumerated value representing an engi-
neering unit of measure
4096 to 65535
BYTE
1
8-bit bitfield
N/A
SHORT_STRING
Up to 128 bytes
Character array where the first byte is the 
number of characters in the array, and the 
subsequent bytes contain the ASCII charac-
ters. This is not a NULL terminated string.
N/A
Table B-7  Mass flow measurement unit codes
Code
Description
70
Grams per second
71
Grams per minute
72
Grams per hour
73
Kilograms per second
74
Kilograms per minute
75
Kilograms per hour
76
Kilograms per day
77
Metric tons per minute
78
Metric tons per hour
79
Metric tons per day