Emerson Network Power Manuel D’Utilisation

Page de 4
 
 
Submittal for SiteI/O 10/0E 
 
  Liebert Corporation
                            Page 1 of 4                                          Rev. 4; 10/03 
 
 
DESCRIPTION: 
The SiteI/O 10/0E is part of the SiteI/O-Line and is intended to be used with 
SiteScan Web systems specifically.  It is a 32 bit microprocessor-based device designed to monitor up to 
ten thermistors, and/or dry contact type signals.  Logically the device, sits on the Ethernet network, 
providing the interface to SiteScan Web.  This effectively creates a device that is a router / gateway and 
I/O module in one device.  Screw terminal blocks are provided to terminate power, communication, and 
input signal wiring.  
 
DIMENSIONS:   
Module: 
7 1/8" H x 6 1/4" W X 1 5/8” D 
 
 
18.10cm H x 15.88cm W X 4.13cm D 
 
 
Enclosure:  
12”H x 14.25" W x 2.85" D 
 
(painted steel) 
419.1mm x 301.3mm x 78.6mm 
 
POWER: 
24 VAC ±10%, 50-60 Hz, 7.2 VA. 
 
ENVIRONMENTAL  
OPERATING RANGE:
0 to 130°F (-17.8 to 54.4°C); 10 to 90% relative humidity, non-condensing. 
For UUKL Smoke Control Systems, 32°-120.2°F (0°-49°C); 10 to 85% relative 
humidity, non-condensing. 
 
COMMUNICATIONS:   
One (1) Ethernet 10BaseT RJ-45 port  
 
MEMORY: 1 MB flash, 1 MB RAM. 
 
BATTERY: Seven-year lithium battery provides a minimum of 10,000 hours of data retention 
during power outages. 
 
FAULT DETECTION:
Hardware watchdog timer. 
PROTECTION: Built-in surge and transient protection circuitry.