5.1.8.
Map Descriptor Example 6: Run-Stop PLC:
This Map Descriptor enables the Driver to give access to the Client to change the Server’s Operating Mode. See
Appendix B.1 for stored values corresponding to PLC modes.
Appendix B.1 for stored values corresponding to PLC modes.
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name
Length
Command_Name
Unit_Number
SRV_RUN_ST,
DA_RUN_ST,
0,
SERVER,
PLC1,
1,
RUN-STOP
0
5.1.9.
Map Descriptor Example 7: CPU Status:
This Map Descriptor enables the Driver to respond to clients requesting CPU status. See Appendix B.1for further
information.
information.
Map_Descriptor_Name,
Data_Array_Name,
Data_Array_Offset,
Function,
Node_Name
Length
Command_Name
Unit_Number
SRV_STATUS,
DA_STATUS,
0,
SERVER,
PLC1,
67,
CPU UNIT STATUS READ
0